background image

Approvals

 

 

 

Description

These kits are for use with Raychem IceStop, XL-Trace and HWAT heating 

cables. The connection is designed to be strapped to the pipe or mounted 

on the wall at the start of the heating cable circuit. These installation 

instructions should be used in conjunction with the IceStop, XL-Trace 

and HWAT System Installation and Operation Manuals. For technical 

support, contact your Tyco Thermal Controls representative or call Tyco 

Thermal Controls (800) 545-6258.

Tools Required

• Utility knife 

• Wire cutters

• TORX

®

 T20 screw driver 

• Wrenches (2)

Additional UL Listed or CSA Certified materials required: 

• 1/2-inch conduit and fittings 

• Junction box

Optional Accessories (not included in this kit):

• RayClic-SB-02 Wall mounting bracket

Ra

yClic

®

F M

AP

PR

OV

ED

wit

h H

WAT

, Ice

Stop

,

and XL-T

race

 he

ating

cables

.

CL I

, D

iv. 2

, G

r. A,

B,C,D

Hazar

dous

 Loc

ations

wit

h G

M-XT 

only

.

WARNING:

Do not open while ener

giz

ed

Shoc

k Hazar

d

718

K Pipe 

Hea

ting Cabl

e

also L

isted

 De-

icing 

and

Sno

w M

elting 

Equi

pment

-W

A

B

C

E

D

F

A

B

C

E

D

F

A

B

C

E

D

F

G

G

G

This component is an electrical device that must be 

installed correctly to ensure proper operation and to 

prevent shock or fire. Read these important warnings 

and carefully follow all the installation instructions.

•  To minimize the danger of fire from sustained electrical 

arcing if the heating cable is damaged or improperly 

installed, and to comply with the requirements of Tyco 

Thermal Controls, agency certifications, and national 

electrical codes, ground-fault equipment protection 

must be used. Arcing may not be stopped by conven-

tional circuit breakers.

•  Bus wires will short if they contact each other. Keep 

bus wires separated.

•  Keep components and heating cable ends dry before 

and during installation.

•  The black heating cable core is conductive and can 

short. It must be properly insulated and kept dry.

•  Component approvals and performance are based on 

the use of Tyco Thermal Controls-specified parts only. 

Do not use substitute parts or vinyl electrical tape.

•  Leave these instructions with end user for reference 

and future use.

A

B

C

E

D

F

A

B

C

E

D

F

A

B

C

E

D

F

G

G

G

A

B

C

E

D

F

A

B

C

E

D

F

A

B

C

E

D

F

G

G

G

RayClic Connection System

RayClic-PC Power Connection and End Seal Kit 

 

RayClic-PS Powered Splice and End Seal Kit 

RayClic-PT Powered Tee and End Seal Kit

 

Installation Instructions

RayClic-PS Powered Splice Kit

Item  Qty  Description 

Item Qty  Description

Powered splice 

D  2  Clips

Pipe mounting bracket  E  2  End seals

Plastic cable ties 

4  Labels 

(1 HWAT, 1 De-Icing &  

 

 

 

 

 

Snow Melting, 2 Warning)

Cable lubricant

RayClic-PT Powered Tee Kit

Item  Qty  Description 

Item Qty  Description

Powered splice 

D  3  Clips

Pipe mounting bracket  E  3  End seals

Plastic cable ties 

4  Labels 

(1 HWAT, 1 De-Icing &  

 

 

 

 

 

Snow Melting, 2 Warning)

Cable lubricant

Kit Contents
RayClic-PC Power Connection Kit

Item  Qty  Description 

Item Qty  Description

Power connection 

D  1  Clip

Pipe mounting bracket  E  1  End seal

Plastic cable ties 

4  Labels 

(1 HWAT, 1 De-Icing &  

 

 

 

 

 

Snow Melting, 2 Warning)

1   Cable lubricant

718K Pipe Heating Cable 

877Z De-Icing and Snow Melting

Not UL Listed with XL-Trace 

heating cable for buried piping.

APPROVED

-w

For HWAT, IceStop, and XL-Trace only

Hazardous Locations: For IceStop (GM-XT) only

Class I, Div. 2, Groups A,B,C,D

Summary of Contents for RayClic-PC

Page 1: ...Arcing may not be stopped by conven tional circuit breakers Bus wires will short if they contact each other Keep bus wires separated Keep components and heating cable ends dry before and during installation The black heating cable core is conductive and can short It must be properly insulated and kept dry Component approvals and performance are based on the use of Tyco Thermal Controls specified p...

Page 2: ...Clic PT powered tee fold up two center snaps then position the connector over the snaps and press down Allow enough extra heating cable to make service loops as required Make sure the end of the heating cable is cut clean For the RayClic PC power connection fold up the four outer snaps then position the connector over the snaps and press down Power Connection Splice and Tee Installation 3 1 8 For ...

Page 3: ... 3 1 8 1 9 For HWAT only Apply HWAT label on insulated hot water tank Using wire cutters cut away 1 inch of the braid Pull exposed braid back over metal clip IceStop and XL Trace HWAT 7 Using wire cutters cut away aluminum wrap Note RayClic connection kits are designed to be installed only once the heating cable cannot be removed once installed Apply a small amout of lubricant to the jacket surfac...

Page 4: ...es the insulation Powered Tee To prevent damage to heating cables protect from sharp cladding edges To prevent water ingress seal the heating cable where it penetrates the insulation Powered Splice To prevent damage to heating cables protect from sharp cladding edges To prevent water ingress seal the heating cable where it penetrates the insulation WARNING Fire hazard Loose screws can cause excess...

Page 5: ...Apply Electric De Icing and Snow Melting label on or near junction box RayClic PC RayClic PS and RayClic PT Mount flat wall mounting bracket under eaves by installing screws through the center holes Do not mount in gutter or where it may be immersed in water Position attachment clips on mounting bracket based on the type of the connector being installed Connect heating cable as detailed in steps 3...

Page 6: ...p and XL Trace Note The end seal is designed to be installed only once it cannot be removed from the heating cable once installed Do not use until ready for final installation HWAT H W A T IceStop and XL Trace 2A 3 Score around and down the outer jacket 1 inch from the end Remove the outer jacket Do not cut or damage the inner jacket Using wire cutters cut away aluminum wrap close to braid and out...

Page 7: ...s Braid clip does not fit Be sure the clip is installed on the metal braid not on the outer jacket Heating cable does not have Only HWAT heating cables have the aluminum wrap under the braid Skip the aluminum wrap aluminum wrap removal step for XL Trace and IceStop heating cables Heating cable cannot be Check for the following inserted into connector Apply cable lubricant to the heating cable prim...

Page 8: ...ntrols only obli gations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product and in no case will Tyco Thermal Controls or its distributors be liable for any incidental indirect or consequential damages arising from the sale resale use or misuse of the product Specifications are subject to change without notice In addition Tyco Thermal Controls reserves the...