background image

2  |  nVent.com  

1.  Prepare the sensing cable prior to installation.

FOR TT5000 SENSING CABLE:

Ensure that the end of the cable is sealed with heat-shrink tubing 

(as it was when supplied from the factory). If the cable end is not 

sealed:
1.  Trim the end of the cable as necessary to remove any irregularities.
2.  Apply a single layer of masking tape 3/4 inch (19 mm) from the end 

of the cable.

3.  Push the fluoropolymer braid back and clip it off back to the  

masking tape (see illustration at right). Take care not to damage 

the black cable jacket; if jacket is damaged, trim the end off and 

begin again.

4.  Slide one of the heat-shrinkable tubes (catalog no. DWP-125-1/4, 

supplied with the bulk reel) over the cable and past the masking 

tape. Remove the masking tape, then position the tube so that 3/8 

inch (9.5 mm) of the tubing extends beyond the end of the cable.

5.  Using a RAYCHEM heat gun or Ultratorch, shrink the tube down to 

bond to the sensing cable. Begin at the end over the cable braid. 

Apply heat long enough to fully recover the tubing, but not so long 

as to melt the braid; do not apply heat directly on the braid, and if 

braid is damaged, begin again. In the middle of the tube, continue 

heating for 10 to 15 seconds after the tubing has shrunk, to ensure 

adhesive in the tubing bonds to the cable jacket. Shrink the entire 

tube, finishing at the end off the cable.

6.  While the tubing end is still hot, use pliers to crimp and seal the end, 

as shown.

7.  Let the tubing and cable end cool a minute or two before  

proceeding with insertion into the Kellems grip.

3/4 in  (19 mm)

Masking tape

Note: Drawings are not to scale

3/8 in (9.5 mm)

SENSING CABLE INSTALLATION IN DOUBLE-CONTAINMENT PIPING

Installation Steps

Bulk sensing cable

Pull

rope

Check that preinstallation requirements have been met before installing sensing cable in double-containment pipe:

1.  The pipe annulus is clean and dry and has been pressure-tested.
2.  A continuous length of 1/4-inch to 3/8-inch (6-mm to 9.5-mm) 

hollow braid polypropylene or nylon rope has been installed from 

access to access of the containment piping as a pull rope.

3.  The pull rope moves freely through the pipe (for example, it is 

not knotted, pinched, or glued to the pipe).

Summary of Contents for TraceTek TT3000 SERIES

Page 1: ...00 Series Bulk Sensing Cable Installation Instructions GENERAL INFORMATION These instructions detail techniques used to install nVent RAYCHEM TraceTek TT3000 or TT5000 bulk sensing cable into double containment pipe Installation is made from pull point access tee to pull point Two people the feeder and the puller are needed to complete the installation They must be able to communicate at all times...

Page 2: ...ugh to fully recover the tubing but not so long as to melt the braid do not apply heat directly on the braid and if braid is damaged begin again In the middle of the tube continue heating for 10 to 15 seconds after the tubing has shrunk to ensure adhesive in the tubing bonds to the cable jacket Shrink the entire tube finishing at the end off the cable 6 While the tubing end is still hot use pliers...

Page 3: ...d locating module 2 Attach Kellems grip to sensing cable 1 Make sure the end of the sensing cable has been properly prepared end of TT5000 sensing cable should be sealed with heat shrink tubing end of TT3000 should be wrapped tightly with electrical tape 2 Insert the end of the cable as far as possible into the cage end of the Kellems grip 3 Tightly wrap electrical tape over 1 in 25 mm of the Kell...

Page 4: ...pipe Use the conduit section to guide the pull rope and sensing cable out of the pipe position it to avoid sharp bends abrasion and snags 5 Pull sensing cable into containment pipe 1 Hold the conduit in position while pulling the cable Begin to pull the rope and cable from the second access point The person feeding the cable must be able to communicate problems such as snags or twisted cable to th...

Page 5: ...till below 20 MΩ it may indicate the cable is bent or crimped which simulates a leak or the cable has been tripped by exposure to a hydrocarbon such as oil or adhesive or the jacket has been damaged and allowed water to enter the braided inner construction A TraceTek Portable Test Box TT PTB 1000 may be used to determine the location of the problem contact your RAYCHEM representative for further i...

Page 6: ...1 5426 3167 cn thermal info nvent com Latin America Tel 1 713 868 4800 Fax 1 713 868 2333 thermal info nvent com nVent com 2018 nVent All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates All other trademarks are the property of their respective owners nVent reserves the right to change specifications without notice RaychemTraceTek IM H55553 TT3000TT5000Bulk EN 1...

Reviews: