DESCRIPTION
These instructions explain the proper procedures for installing and testing
nVent RAYCHEM TraceTek TT500X-HS sensing cables. (TT500X-HS refers
to either TT5000-HS or TT5001-HS). TT500X-HS sensing cables are primarily
intended for use in underground (fuel or solvent) pipeline applications. TT500X-
HS sensing cables ignore water but will detect and locate (fuel or solvent) spills
and leaks. (See the data sheet for specific performance characteristics.)
Important Notes
When used to monitor underground fuel pipelines, TT500X-HS sensing cables
are typically installed within slotted conduit that is routed alongside the main
pipeline. TT500X-HS sensing cable is designed for use within slotted PVC
conduit and is constructed with an outer layer of polyethylene fibers to provide
extra pulling strength and low friction during the installation process. The
sensor cable core is standard TT5000 (for fuel) or TT5001 (for solvent) with
well documented response times, numerous third party qualifications and years
of successful applications.
• TT5000-HS sensing cable is identified by the all white color of the outer jacket.
• TT5001-HS sensing cable is identified by a purple TRACER in the white
outer jacket.
GENERAL NOTES: DO’S AND DON’TS:
TOOLS REQUIRED
nVent RAYCHEM TraceTek
TT-PTB-1000
(part # 486437-000)
Portable Test Box, battery powered instrument
specifically designed for testing and trouble
shooting TraceTek systems
Ohmmeter
(>20 M ohm)
Can be used as an alternative and supplement to
the PTB 1000
nVent RAYCHEM TraceTek
TT-MAPPING CAP-MC
(part # P000000871)
Used to simulate leaks at connector points during
commissioning and mapping process
Extran Vent RAYCHEM
TraceTek TT-MLC-MC-BLK
(part # 133332-000)
Leader cable. Used with the ohmmeter to make
connections to the sensor cable for resistance
measurements
Extra TT-MET-MC
(part # 571293-000)
End termination. Used during installation or trouble
shooting to temporarily isolate a sub-section of
sensor cable for resistance measurements.
nVent RAYCHEM TraceTek
TT-Kellems-Grip-Large
(part # P000001291)
Large Kellems Grip used in cable pulling when rope
overbraid loop not available.
nVent RAYCHEM TraceTek
TT-ULTRA-TORCH
(part # 390067-000)
Flameless heating tool (Ultratorch 200) or suitable
heat gun with concentrator tip
REQUIRED MATERIALS
Conduit cleaning tool
Used in proofing installed sections of conduit.
Conduit end caps
Used to cover exposed conduit end to maintain
conduit cleanliness.
Heat shrink tubing
segments
Used as environmental seal over all mated male/
female (pin/socket) connections
OPTIONAL MATERIALS
nVent RAYCHEM TraceTek
TT-MBC-MC-TW
(part # P000001206)
Branch connector designed for rugged outdoor
applications used to connect and branch "T" lines
nVent RAYCHEM TraceTek
TT-MJC-XX-MC-BLK
Jumper cable is available in various pre-cut and
terminated lengths
nVent RAYCHEM TraceTek
TT5000–HUV–CK–
MC–M/F
(part # P000001207)
Connector kit used during field connection of
TT500X-HS bulk cable
TraceTek Sensing Cable for Underground Leak Detection
Installation Instructions
TT5000-HS
(for fuel leaks)
TT5001-HS
(for solvent leaks)
DO:
• Store the cable in its original container in a clean, dry area until ready to install.
• Schedule the sensor cable installation as late as possible in the construction
schedule to avoid risk of damage or contamination by other contractors or
construction tasks.
• Remove cable from the pipe if any thread cutting, welding, soldering or similar pipe
fitting work will be performed.
DON’T:
• Drag the cable through water, paint, solvents, oil or other contaminants.
• Install damaged or contaminated sensing cable.
• Exceed the maximum pulling force of 100 kg (220 lb).
• Use the cable as a rope for lifting or securing any object.
• Allow tools or heavy objects to fall on cable.
• Exceed 3300 ft (1000 m) of individual sensor cable circuit length when using a SIM
alarm module.
• Test the cable with fuel. • Use tie wrap or wire to secure the cable.