PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
2 of 44
www.tycothermal.com
H55838 2/12
This guide does
not
cover applications in which any of the following conditions exist:
• Hazardous locations, as defined in the national electrical codes
• Pipe temperature other than specified in Table 1 on page 3
• Pipe maintenance temperatures above 150°F (65°C)
• Supply voltage other than 120 V or 208–277 V
If your application conditions are different, or if you have any questions, contact your
Tyco Thermal Controls representative or contact Tyco Thermal Controls directly
at (800) 545-6258 .
How to Use this Guide
This design guide presents Tyco Thermal Controls’ recommendations for designing an XL-Trace
pipe freeze protection or flow maintenance system . It provides design and performance data,
electrical sizing information, and application configuration suggestions . Following these
recommendations will result in a reliable, energy-efficient system .
OTHER REquIRED DOCuMEnTS
This guide is not intended to provide comprehensive installation instructions . For complete
XL-Trace pipe freeze protection and flow maintenance system installation instructions, please
refer to the following additional required documents:
•
XL-Trace System Installation and Operation Manual
(H58033)
• Additional installation instructions are included with the connection kits, thermostats,
controllers, and accessories
If you do not have these documents, you can obtain them from the Tyco Thermal Controls
web site at www .tycothermal .com .
For products and applications not covered by this design guide, please contact your Tyco
Thermal Controls representative or call Tyco Thermal Controls directly at (800) 545-6258 .
Safety Guidelines
As with any electrical equipment, the safety and reliability of any system depends on the
quality of the products selected and the manner in which they are installed and maintained .
Incorrect design, handling, installation, or maintenance of any of the system connection kits
could damage the system and may result in inadequate performance, overheating, electric
shock, or fire . To minimize these risks and to ensure that the system performs reliably, read
and carefully follow the information, warnings, and instructions in this guide .
This symbol identifies important instructions or information .
This symbol identifies particularly important safety warnings that must be followed .
WARnInG
: To minimize the danger of fire from sustained electrical arcing if the
heating cable is damaged or improperly installed, and to comply with the requirements of
Tyco Thermal Controls, agency certifications, and national electrical codes, ground-fault
equipment protection must be used on each heating cable branch circuit . Arcing may not
be stopped by conventional circuit protection .