55M4000BCE00 REV A
29
3.8 “Transfer” restoring calibration
Warning:
This procedure will overwrite the existing data in the i4000 system and the
existing data will be lost. It is advisable to archive copies of the existing data using the
procedure in step #16 as a precaution before continuing. If in doubt consult Rayco
Wylie.
A copy of the calibration and/or load chart files can be restored to the i4000 system at
any time.
Note
a USB memory stick must be connected to connector ‘USB’ of the i4000
display unit using a Deutsch to USB converter lead (RaycoWylie part no. 33V0338)
before proceeding. Ensure the file required to be restored is saved in the root folder of
the USB stick.
Navigate through the calibration menu using
“
”
or
“
”
to highlight “transfer” and
press
“
”
to enter.
Select “USB to Calibration” ” and press
“
”
A list of files will be displayed,
“xxxx.cal”
. Note that only files located in the root folder
of the USB stick will be displayed. Select the relevant file from the list displayed and
press
“
”
, the selected file will be copied to the i4000 system and will replace any
existing data.
Once done, it is advisable to reboot the system (power off and on again).