background image

19

Gas Supply

Gas piping 

must

have a sediment trap ahead of the

heater gas controls, 

and

a manual shut-off valve lo-

cated  outside  the  heater  jacket.  It  is  recommended

that a union be installed in the gas supply piping adja-

cent  to  the  heater  for  servicing.  The  gas  supply

pressure to the heater must not exceed 10.5 in. WC for

natural gas or 13.0 in. WC for propane gas. A pounds-

to-inches regulator must be installed to reduce the gas

supply pressure if it is higher than noted above. This

regulator should be placed a minimum distance of 10

times  the  pipe  diameter  upstream  of  the  heater  gas

controls. Refer to Table H for maximum pipe lengths.

Gas Supply Connection

The heater must be isolated from the gas supply pip-

ing  system  by  closing  the  upstream  manual  shut-off

valve  during  any  pressure  testing  of  the  gas  supply

piping system at test pressures equal to or less than

1/2  psi  (3.45  kPa).  Relieve  test  pressure  in  the  gas

supply  line  prior  to  re-connecting  the  heater  and  its

manual shut-off valve to the gas supply line. 

FAILURE

TO  FOLLOW  THIS  PROCEDURE  MAY  DAMAGE

THE  GAS  VALVE

.  Over-pressurized  gas  valves  are

not covered by warranty. The heater and its gas con-

nections  shall  be  leak-tested  before  placing  the

appliance in operation. Use soapy water for leak test.

DO NOT use an open flame.

DANGER:

Make sure the gas on which the heater

will  operate  is  the  same  type  as  specified  on  the

heater’s rating plate.

CAUTION:

The heater must be disconnected from

the gas supply during any pressure testing of the gas

supply system at test pressures in excess of 1/2 psi

(3.45 kPa). 

Gas Supply Pressure

A  minimum  of  4.0  in.  WC  upstream  gas  pressure

under full load and a maximum gas supply pressure

setpoint of 10.5 in. WC under load and no-load condi-

tions  for  natural  gas.    A  minimum  of  4.0  in.  WC

upstream gas pressure under full load and a maximum

gas supply pressure setpoint of 13.0 in. WC is required

for propane gas.  The gas pressure regulator(s) sup-

plied  on  the  heater  is  for  low-pressure  service.    If

upstream  pressure  exceeds  1/2  psi  at  any  time,  an

intermediate  gas  pressure  regulator,  of  the  lockup

type,  must  be  installed.    This  regulator  should  be

placed a minimum distance of 10 times the pipe diam-

eter upstream of the heater gas controls.

When connecting additional gas utilization equipment

to the gas piping system, the existing piping must be

checked to determine if it has adequate capacity for

the combined load.

The  gas  valve  pressure  regulator  on  the  heater  is

nominally preset as noted in Table I. 

During  normal  operation,  carbon  dioxide  should  be

9.0%  ±  0.2%  at  full  fire  for  natural  gas  and

10.2%  ±  0.2%  for  propane  gas.    Carbon  monoxide

should be ‹100ppm at all firing rates, measured at the

test port, 12” above the flue collar.

Fig. 17: Gas Supply Connection

CAUTION:

Do not use Teflon tape on gas line pipe

thread. A pipe compound rated for use with natural

and  propane  gases  is  recommended.  Apply

sparingly  only  on  male  pipe  ends,  leaving  the  two

end threads bare.

CAUTION:

Support  gas  supply  piping  with

hangers, not by the heater or its accessories. Make

sure  the  gas  piping  is  protected  from  physical

damage and freezing, where required.

Summary of Contents for 503A

Page 1: ...vapors and liquids or other combustible materials in the vicinity of this or any other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any applian...

Page 2: ...ble K on page 29 Table M on page 32 Wiring Diagram on page 43 Blower Check on page 46 Table T on page 46 Manifold Check on page 46 Filter Maintenance on page 54 Additions Motorized Combustion Air Damp...

Page 3: ...Hot Water 17 Gas Supply 19 Electrical Power Connections 20 Field Wiring Connection 21 Venting 26 Venting Installation Tips 28 Venting Configurations 28 Outdoor Installation 33 Controls 34 User Interfa...

Page 4: ...cause cancer birth defects or other reproductive harm WARNING Risk of electrical shock More than one disconnect switch may be required to de energize the equipment before servicing CAUTION This heater...

Page 5: ...nly per Raypak s standard war ranties Model Identification The model identification number and heater serial number are found on the heater rating plate located on the upper rear jacket panel of the h...

Page 6: ...cations Top Fig 3 Component Locations Rear Panels omitted for clarity Fig 2 Component Locations Front Model No MBTUH Input Water Conn NPT Gas Conn NPT Vent Size in Max Min N P Flue Intake 503A 500 70...

Page 7: ...To determine the water temperature being delivered turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer NOTE When this water heater is supplying general...

Page 8: ...n in front 1 in on the side at least 24 in on the rear and 10 in above the top of the heater is required This will allow 8 Table C Clearances Indoor Installations INSTALLATION Installation Codes Insta...

Page 9: ...erhang unless clearances are in accordance with local instal Combustion and Ventilation Air Indoor Units This heater must be supplied with sufficient quantities of non contaminated air to support prop...

Page 10: ...t 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above paved sidewalk or paved driveway located on public property 7 ft 2 13m...

Page 11: ...g connection section of this manual for proper wiring instructions using Fan Damper dry contacts and external interlock TruSeal Combustion Air In addition to the 3 previous steps combustion air may be...

Page 12: ...l be provided by an opening s for ventilation air at the highest practical point communicating with the outdoors The total cross sectional area of such an opening s shall be at least 10 of the area re...

Page 13: ...changer with water temperatures as low as 120 F 49 C Heaters operated with an inlet temperature of less than 120 F 49 C MUST have an approved low tem perature operation system Figs 10 and 11 to preven...

Page 14: ...water source heat pump applications as well as some others An injector pump arrangement may be used to keep the heater loop at or above 120 F 49 C An injector pump approach has the added value of bei...

Page 15: ...range of applications The installer design engineer should refer to the following Modes to determine which best fits the intended application and functionality for the unit being installed Type H mode...

Page 16: ...lower than the WWSD temperature setting if utilized unless an indirect call for heat is present with priority Fig 12 MODE 1 Single Boiler with Primary Secondary Piping Fig 14 MODE 2 Single Boiler with...

Page 17: ...lieu of the Indirect DHW Sensor S5 See the Versa IC manu al for additional details Domestic Hot Water When designing the water piping system for domestic hot water applications water hardness should...

Page 18: ...ains per gallon a water softener treatment system must be utilized Caution For scale free operation with Hard Water 16 25 grains per gallon of total hardness the operating control must NOT be set high...

Page 19: ...s supply during any pressure testing of the gas supply system at test pressures in excess of 1 2 psi 3 45 kPa Gas Supply Pressure A minimum of 4 0 in WC upstream gas pressure under full load and a max...

Page 20: ...to Terminals 1 2 and 3 as noted in Fig 18 All low voltage wiring including sensors interlocks enable disable and var ious options are wired into terminals 1 24 on the front wiring panel as noted in F...

Page 21: ...Connected Controllers It is strongly recommended that all individually pow ered control modules and the heater should be supplied from the same power source NOTE Field supplied isolation relays should...

Page 22: ...up to 150 feet 4 Mount the outdoor sensor on an exterior surface of the building preferably on the north side in an area that will not be affected by direct sunlight and that will be exposed to varyin...

Page 23: ...tion 2 When the Indirect DHW call for heat is active the PIM communicates this to the VERSA The VERSA calculates the optimal operation and sends the firing rate and pump output requests to the PIM so...

Page 24: ...nnections are dry contacts rated for pilot duty only 5A maxi mum 2 Connect the boiler pump enable wires to the termi nal block at the rear of their unit The connections are dry contacts rated for pilo...

Page 25: ...pump outputs are not used in the Cascade Follower configuration Fig 27 VERSA Follower Modbus BMS Communication The VERSA IC control is equipped as standard with a communications port for connectivity...

Page 26: ...ANSI Z21 Standard and the NFGC U S or B149 Canada or applicable provisions of local building codes WARNING Contact the manufacturer of the vent material if there is any question about the appliance ca...

Page 27: ...exterior finishes Use a rust resistant sheet metal backing plate against brick or mason ry surfaces 12 DO NOT extend exposed vent pipe outside of building beyond the minimum distance required for the...

Page 28: ...r door which can be opened in any building any non mechani cal air supply inlet to any building or the combustion air inlet of any other appliance 8 Underneath a verandah porch or deck unless the vera...

Page 29: ...The horizontal portions of the vent shall also be supported for the design and weight of the material employed to maintain clearances and to prevent physi cal damage or separation of joints NOTE A ven...

Page 30: ...NOT it MUST be replaced NOTE For extractor sizing typical CO2 levels are 9 0 for natural gas and 10 2 for propane gas and flue temperature of 300 F at 100 firing rate meas ured at test port 12 above...

Page 31: ...tallation These installations utilize the heater mounted blower to vent the combustion products to the outdoors Combustion air is taken from inside the room and the vent is installed horizontally thro...

Page 32: ...t vent cap must be used sales order option D 15 The vent terminal must be located NO CLOSER than 12 off the wall Table M Category IV Horizontal Vent Horizontal Direct Vent Direct Vent Vertical Install...

Page 33: ...eaves debris etc The stainless steel flue direct vent cap must be fur nished by the heater manufacturer in accordance with its listing sales order option D 15 Outdoor Installation Outdoor models must...

Page 34: ...e equipment before servicing NOTE Condensate can freeze on the vent cap Frozen condensate on the vent cap can result in a blocked flue condition Ignition Control Functions When there is a call for hea...

Page 35: ...of the gas valve on the inlet flange to the gas valve and is accessible through the removable access panels on the side or front of the heater to reset the gas pressure switch as necessary It is used...

Page 36: ...C Control I O Manual Catalog 5000 72 Adjusting the MVB Setpoint To adjust the setpoint on the MVB Use the MENU key to scroll to the SETUP ADJUST menu then use the ITEM key to scroll to the SET POINT i...

Page 37: ...3 Current system supply temperature Boil OUTLET All Current boiler outlet temperature Boil INLET All Current boiler inlet temperature Boil T All Current temperature difference between boiler outlet an...

Page 38: ...rature 220 F TARGET MIN H MODE 1 2 3 OFF 50 F to 190 F Minimum target system temperature 50 F TARGET DIFF H MODE 1 2 3 2 F to 42 F Differential for target system temperature 10 F DHW SENSOR H MODE 1 2...

Page 39: ...fset OPERATOR All Operator Limit Potentiometer PIM setting AUTO DIFF H MODE 1 2 3 Current auto differential PUMP PREPt All Duration of pump prepurge BLOW PREPt All Duration of blower prepurge BLOW PRE...

Page 40: ...oiler outlet temperature Press UP DOWN for 1 sec to clear INLET HI All Records the highest boiler inlet temperature Press UP DOWN for 1 sec to clear INLET LO All Records the lowest boiler outlet tempe...

Page 41: ...degree the outdoor temperature drops the tempera ture of the heating water will increase one degree With the VERSA both ends of the slope are adjustable It is factory set at 70 F water temperature Bo...

Page 42: ...ual temperature where the building is located This temperature is used when completing heat loss calculations for the building Boiler Design Boil DESIGN The Boil DESIGN temperature is the water temper...

Page 43: ...43 WIRING DIAGRAM Models 503A 2003A...

Page 44: ...Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only your hand to turn the gas control valve handle Never use tools If the handle will not tur...

Page 45: ...roximately 15 seconds after the blower starts the igniter should start to glow observable through the observation port located at the front below the gas valve Look into the sight glass located just b...

Page 46: ...ion USER TEST is displayed in the Title Field UP keystrokes are used to advance through the user test The Boil MIN MAX steps for burner operation are only run for enabled boilers Local Heat DHW EMS de...

Page 47: ...point B bleedle valve and open the upstream manual gas valve Make sure that test point A B bleedle valves have been opened so as to allow gas to flow This will bring gas pressure to the second valve s...

Page 48: ...allow one time operation of the limit and then must be returned to normal operation by turning dip switch 8 back to the OFF position Power to the unit must then be cycled off then on to return to nor...

Page 49: ...ater temperature or manual reset high limit is not tripped c Enable Disable circuit is closed d Gas is on at the meter and the heater e Incoming dynamic gas pressure to the gas valve is NOT less than...

Page 50: ...replace control DELTA T Temperature difference between the inlet and outlet exceeded the set point Check water flow LOW 24VAC Low 24 VAC power Check power supply wiring and transformer BLOW SPEED Blow...

Page 51: ...the gas supply See table for more information 4 flashes N A N A 5 flashes Low Voltage Fault Check the 24 VAC input voltage The voltage must be above 18 0 VAC 6 flashes N A N A 7 flashes Hi Limit Fault...

Page 52: ...c tion deterioration or leakage 4 Visually inspect for proper operation of the con densate drain in the venting If leaks are observed repair at once 5 Check air vents for leakage Yearly Beginning Of E...

Page 53: ...see light blue flame at full input rate Weekly For low pressure heaters test low water cut off device With heater in pre purge depress the low water cut off test button Appliance should shut off and i...

Page 54: ...sure Vessel Code Section IV Filter Maintenance Inspect quarterly Replace when tracking pressure exceeds 0 5 in WC at 100 fan speed except for models 1003A 1753A and 2003A which need to be replaced whe...

Page 55: ...ontaminated ar eas this may also experience deterioration Products causing contaminated combustion air spray cans containing chloro fluorocarbons permanent wave solutions chlorinated waxes cleaners ch...

Page 56: ...wall horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth...

Page 57: ...PLACEMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned to Raypak if requested with transportation charges prepaid and all applicable...

Page 58: ...utes Vent Size _____________ Stack Height _______ Low Water Cutoff _______________Test Category _________ sketch vent on reverse side Number of Tanks and Size Qty____ _______Gallons Vent Material ____...

Page 59: ...59...

Page 60: ...60 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Reviews: