8
HIGH WIND LOAD RESTRAINT DETAIL 1
PAD SPECIFICATION:
GREATER THAN OR EQUAL TO 4" THICK SOLID CONCRETE 2000 P. S. I. OR GREATER LOAD RATING
PAD LENGTH GREATER THAN OR EQUAL TO 42.5" (108 cm)
PAD WIDTH GREATER THAN OR EQUAL TO 42.5" (108 cm)
MINIMUM 16 GA. X 3.75” WIDE STAINLESS STEEL
TIE DOWN (MIN. QTY. OF 4 TIE DOWNS) WITH (3)
1/2” LONG #12 SELF DRILLING SCREWS EACH
STRAP (MIN. 1000 HR. COATING)
(2) 1/4” CONCRETE SCREWS
LENGTH TO PENETRATE
2-3/8" (6 cm) MINIMUM.
CONCRETE PAD
(SEE PAD SPECS.)
UNIT
SEE HIGH WIND LOAD
RESTRAINT DETAIL 1
RESTRAINT
SET AT EACH
CORNER
3" MIN. (7.6 cm)
SPACING TYP.
COVERED UNIT
HEIGHT BETWEEN
37-1/2" - 42-13/32" (95-107.7 cm)
WITH PLASTIC
BASE PAN
THIS DRAWING USED AS A GRAPHICAL REPRESENTATION ONLY
AND IT MAY NOT APPEAR EXACTLY LIKE YOUR SPECIFIC UNIT.
THIS DRAWING INTENDED FOR POOL HEATERS ONLY!
QT Model Hurricane Tie Down Specifications
Figure 3. QT Model Hurricane Tie Down Specifications
5. ELECTRICAL
CONNECTIONS
Refer to the rating plate below the control panel for precise
power requirements for your unit, and for ampacity and
over-current protection requirements.
All wiring must be in accordance with the National Electrical
Code, NFPA No. 70, latest edition, and all applicable state
and local codes. Wiring diagrams are located on
pages
19 through 23
.
NOTE:
Refer to the National Electrical Code, Article
680, for general requirements for swimming pools and
equipment, and to Article 440 for special considerations
necessary for circuits supplying hermetic refrigeration
motor/compressors.
• Locate the equipment disconnect means within 3
feet (91 cm) of the heater’s electrical enclosure, or
as close to the heater as possible. Always satisfy
applicable codes and standards.
• In sizing power wiring, be especially aware of up-sizing
requirements necessary due to wiring distances.
Always satisfy applicable codes and standards.
• Electrical installation should be done by a licensed
electrician only.
This unit is pre-wired to work with external control
systems, heat-on-demand options and other external time
clock overrides. Refer to the external control system’s
instructions, and
page
24
of this manual, for installation
information.
Summary of Contents for 5350 Series
Page 20: ...20 H C F DUAL CAPACITOR V V 208V 230V Single Phase Digital Models 5350 6350 8350 8360...
Page 21: ...21 208V 230V 3 Phase Analog Models 5350 6350 8350...
Page 22: ...22 208V 230V 3 Phase Digital Models 5350 6350 8350...
Page 23: ...23 460V 3 Phase Analog Model 8354...
Page 26: ...26...
Page 28: ...28...
Page 29: ...29...
Page 30: ...30 NOTES Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com...
Page 60: ...30 NOTES Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com...