9
Model No.
VAC - Phase -
Hz
Minimum
Circuit
Ampacity
(A)
Breaker
Size
(A)
Min Max
5350
208/230 - 1 - 60
40.0
50
60
6350/6350HC
42.0
8350/8350HC
208/230 - 3 - 60
34.0
40
50
10355
208/230 - 1 - 60
42.0
40
60
Table B. Electrical Power Requirements
6. WATER CONNECTIONS
CAUTION:
The heater inlet and outlet connections
are NOT interchangeable. They must be connected as
instructed below.
1. Connect the heater in the return water line between
the filter and the pool/spa. See the Plumbing
Diagrams beginning on
page
15
.
2. Connect the filter outlet to the fitting marked WATER
IN at the bottom front of the unit.
3. Connect the fitting marked WATER OUT to the return
piping to the pool/spa. Unit inlet/outlet connection
fittings are 2" PVC unions.
Water connections from the unit to the main return line can
be PVC pipe or flexible pipe approved for the purpose and,
in either case, should be at least equal in size to the main
pool/spa circulation piping.
WATER IN
WATER OUT
Figure 4. Water Connections
4. In cold weather (freeze zone) areas, shutoff valves
(ball or gate type) must be installed at the unit inlet
and outlet to facilitate service and cold weather drain-
down.
5. Operate the pump and check the system for leaks.
7. PRESSURE DROP
For system pressure drop information, refer to
Table C
below.
Flow
gpm (lpm)
Pressure Drop PSI (kPa)
5350
6350/6350HC 8350/8350HC/
8360
30 min. (114) 4 (27.6)
6 (41.4)
9 (62.1)
40 (151)
7 (48.3)
9 (62.1)
9 (62.1)
50 (189)
10 (68.9)
10 (68.9)
10 (68.9)
60 (227)
11 (75.8)
11 (75.8)
11 (75.8)
70 (265)
12 (82.7)
12 (82.7)
12 (82.7)
80 max. (303) 13 (89.6)
13 (89.6)
13 (89.6)
Multiply the pressure drop in PSI by 2.3067 to yield the pressure drop
in Ft. H2O Head (TDH).
Table C. Pressure Drop Across Heater
A
WARNING:
Install a check valve and/or a Hartford
loop AFTER the heater and BEFORE any chlorinating
devices. Install any automatic chemical feeders AFTER
the heater. Improper installation of any type of automatic
chemical feeders can result in serious damage to, or
premature failure of the heater. Such damage will not be
covered under warranty.
8. CONTROLS & INDICATOR
LAMPS (ANALOG
MODELS)
Your analog heater incorporates safety controls and
indicators to ensure its safe, reliable operation (for models
with digital controls, see
page 11
).
Water Pressure Switch
: Prevents operation when the
pump is OFF. The unit requires 5 PSI (34.5 kPa) minimum
pressure.
Water Temperature Control
: Pool/spa water temperature
is controlled by the heater thermostat on the unit control
panel, which contains a switch and 2 thermostats, one
for setting a heat spa temperature and the other for a
swimming pool temperature. The switch can operate an
optional external control system, or can switch between
thermostats for pool or spa.
NOTE:
The heater will not run when the Remote position
is selected on the Pool/Spa selector switch and there is
no remote control system attached.
Defrost Switch
: Prevents operation of the heater if
ambient air temperature falls below a predetermined safe
minimum (approximately 42°F [5.6°C]).
Delay Time
r: Prevents the compressor from short-cycling,
which could damage or destroy the hermetic motor/
compressor. Upon water temperature control satisfaction,
or other circuit interruptions, this solid-state device will
prevent compressor restart for approximately 5-minutes.
Summary of Contents for 5350 Series
Page 20: ...20 H C F DUAL CAPACITOR V V 208V 230V Single Phase Digital Models 5350 6350 8350 8360...
Page 21: ...21 208V 230V 3 Phase Analog Models 5350 6350 8350...
Page 22: ...22 208V 230V 3 Phase Digital Models 5350 6350 8350...
Page 23: ...23 460V 3 Phase Analog Model 8354...
Page 26: ...26...
Page 28: ...28...
Page 29: ...29...
Page 30: ...30 NOTES Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com...
Page 60: ...30 NOTES Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com...