PART 2 - SECTION I - 
INSTALLATION INSTRUCTIONS

Before commencing installation:

1.

Read these instructions in full !

2.

Check  that the heater you have

been supplied is suitable for the type of
installation and the gas available. The gas
supply pressure must be between the
minimum and maximum shown on the
heater data plate.

GENERAL

These instructions are provided to ensure the
correct installation and operation of your
Raypak Swimming Pool Heater.

Should any questions arise regarding the
specifications, installation, operation or
servicing of this heater, we suggest that the
local representative or Raypak Customer
Service be consulted.

Raypak heaters utilise a finned copper tube
heat exchanger resulting in a low water content
and reduced "stand by" heat losses. Therefore
a circulator pump of sufficient capacity to
match the heater model must be installed in
the system.

Raypak heaters are fitted with Australian Gas
Association approved components and all
boilers in this range are designed to comply
to AG501.

Some models are designed for either indoor or
outdoor installation subject to the appropriate
indoor draft hood or outdoor stackless top
being fitted.

Check that the correct top for your installation
has been supplied.

INSTALLATION PROCEDURES

All electrical, gas piping, gas connection and
flueing of the heater must only be undertaken
by a properly authorised person. The
installation must comply with local gas, AG601-
2000  and electrical  codes and/or statutory
body codes and regulations.

Raypak heaters must be installed in the
filtration system, in the pool return line,
downstream from the filter.

INSPECTION OF EQUIPMENT

Check the heater and associated equipment for any
damage and if so notify your  local representative or
Raypak for any further instructions.

DO NOT INSTALL OR START UP ANY
RAYPAK SUPPLIED PRODUCT THAT HAS

BEEN DAMAGED, WITHOUT FIRST
CONSULTING RAYPAK, AS ANY DAMAGE
OR FAULTS CAUSED BY UNAUTHORISED
START UP MAY NOT BE COVERED BY
OUR WARRANTY.

HEATER LOCATION AND
CLEARANCES

The heater should be located so that any
possible water leaks will not cause damage to
any adjacent areas or structures.

When such locations cannot be avoided, it is
recommended that a suitable drain pan,
adequately drained, be installed under the heater.

This pan must not restrict combustion air flow.

The heater must be mounted on a level non-
combustible base such as a concrete slab,
concrete plinth, steel plate etc.

Raypak heaters and equipment must not be
installed on carpeting.

The front of the heater must not be obstructed
by any gas or water piping, electrical conduits,
trees, fences, or other equipment, etc.

COMBUSTION/VENTILATION
AIR

Indoor model heaters must only be installed in
a protective enclosure or properly constructed
plant room with adequate ventilation in
accordance with AG 601 - 2000 Gas
Installation Code.

Ventilation shall be via 2 permanent openings
directly to outside, one at an upper level and
one at low level.

The minimum free area provided by each vent
shall be as calculated by using the following
formula, unless otherwise stated in AG 601.

A =1.5 X T

Where A = Minimum free ventilation area (cm2)

T = Total hourly input of all appliances (Mj/h)

Note: The minimum dimension of any opening
shall be 6mm.

Please take the heater location into account
when locating the fresh air vents because any
excessive draft will cause flame disturbance
and probable pilot outage. In some cases
where excessive draft effects the burner, the
risk of major damage is high due to
incomplete combustion.

Installations which obtain air from a source
other than directly from outside must comply
to AG601.

Warning: Air supply to the heater room
must not be affected by mechanical
exhaust vents located in other parts of
the house or building, such as kitchen or
bathroom fans, spa blowers, etc.

Mechanical exhaust vents may create a negative
pressure in the heater room that can become a
hazard by asphyxiation, explosion or fire.

Caution: Do not store chemicals or flammable
materials in the same room or near this
heater. Do not use aerosols near this heater
whilst it is in operation.

FLUEING

The correct Draft hood must be fixed to the top
of the heater and connected to a properly
constructed flue, vented to the outside using
only approved fittings.

Reduction of the flue diameter or alteration to
the draft hood voids all warranty. Where
flueing may be difficult, please contact Raypak
for advice, we will have solutions, particularly
where a fan assisted flue may be the answer.

The weight of the flue must not rest on the
heater draft diverter, the flue must be self
supporting and be fitted with a disconnection
section (bolted sleeve) to enable the heater top
and draft diverter to be removed easily, for
servicing. Where practicable the flue should run
vertically. Lateral (raised above horizontal) is
acceptable but the run of a flue shall not
exceed 50% of total flue height and shall be
designed to rise not less than 20 mm per 1 m
run. The flue must be terminated with an
approved cowl.

Summary of Contents for 538 To 4224

Page 1: ...Raypak Commercial Swimming Pool Heaters Part 1 Safety warning Part 2 Models 538 to 4224 Part 3 Warranty...

Page 2: ...tion and maintenance of your Raypak Heater Please review and follow these procedures carefully Keep this manual in a safe and accessible place for easy reference in the future Part 2 Models 538 to 422...

Page 3: ...Turn off the gas supply at the gas meter Immediately call your gas supplier or licensed gasfitter NOTE Some gases are heavier than air and it may be necessary to check for gas leaks at floor level DO...

Page 4: ...Safety Authority for any further information Rinse any exposed skin areas with clean water Wash work clothing separately FIRST FIRING OF HEATER Fumes and smoke may be produced Avoid breathing fumes ve...

Page 5: ...6 Raypak Commercial Swimming Pool Heaters Part 2 Models 538 to 4224...

Page 6: ...crete plinth steel plate etc Raypak heaters and equipment must not be installed on carpeting The front of the heater must not be obstructed by any gas or water piping electrical conduits trees fences...

Page 7: ...etails Caution The gas supply must be isolated from the heater during pressure testing of the gas fitting line Dissipate test pressure before reconnecting to the heater Failure to follow this procedur...

Page 8: ...the pipework Please insert the sensor as shown in the drawing below ELECTRICAL WIRING The electrical power consumption of the heaters is Models 538 1292 No By Pass Pump 240 Volts AC 50 60 Hz 100 VA ap...

Page 9: ...fied that the pressure switch has not closed Adjust the pressure setting at the thumbwheel to a lower setting then re start the heater If the heater fires up but won t shutdown when the water is reduc...

Page 10: ...part or control system that has been under water Always keep the heater clean and the surrounding area clear of all combustible and flammable materials Remove all dangerous liquids and chemicals from...

Page 11: ...e alarm on fail which can be silenced by pressing the reset button however the light will remain illuminated until the cause of the failure has been reset 3 ALARM SIREN This is used in conjunction wit...

Page 12: ...layed It must be a negative value Press the UP or DOWN button to set your desired differential This is adjustable from 1 to 25 which relates to 1 to 25 Deg C LAE ELECTRONIC THERMOSTAT DEFAULT SETTINGS...

Page 13: ...ely essential that your pool water is chemically balanced WARRANTY PROCEDURE FOR WATER LEAKS FROM HEAT EXCHANGER 1 The service technician inspects the tube bundle if the water leak is through one or m...

Page 14: ...d louvres clean as required Restore gas electricity and water as required Recommission unit check and prove the operation of all safety devices Check and monitor the operation of the appliance for at...

Page 15: ...Deg C pH 7 3 to 7 4 7 3 to 7 4 7 6 to 7 8 Total Alkalinity 120 to150 120 to 150 150 to 200 ppm Calcium Hardness 200 to 300 150 to 200 80 to 100 ppm Salt Level ppm 6000 Maximum 6000 Max 6000 Max Free C...

Page 16: ...in Raypak Pool Heater literature WARRANTY EXCLUSIONS 1 REPAIR AND REPLACEMENT WORK WILL BE CARRIED OUT AS SET OUT IN THE RAYPAK POOL HEATER WARRANTY ABOVE BUT THE FOLLOWING EXCLUSIONS MAY CAUSE THE P...

Page 17: ...18 NOTES...

Page 18: ...RHEEM SERVICE 131 031 WWW RHEEM COM AU Quality System Quality Endorsed Company Manufactured by Raypak Australia 7 Geddes St Mulgrave Vic 3170 Ph 03 9535 3333 Fax 03 9560 4974 JAN 2003 P NO 96209131...

Reviews: