ADVANCED PROGRAMMING
ADVANCED PROGRAMMING
ADVANCED PROGRAMMING
ADVANCED PROGRAMMING
Default DIP Switch settings on the AR-401RO16B are as follows:-
Floor Access is determined by the Node ID, which is set by Dip Switches 1 to 4. The Node ID
of the AR-401RO16 must be set up to one of the following numbers.
ID 1 = Floors 1 - 16
ID 2 = Floors 17 - 32
ID 3 = Generally Not Used
ID 4 = Floors 33 - 48
ID 5 = Floors 49 - 64
The Baud Rate is the communication speed between the AR-401RO16 and the associated
access controller. The Baud Rate must be set to 4800 (Switches 5 on and 6 off).
All Relay outputs can be set so all Relays are Normally Open or Normally Closed via the DIP
Switch. DIP Switch 8 sets the state of all the Relays, in addition individual Relays can be set
to Normally Open or Normally Closed separately via the Jumpers on each relay circuit.
The default setting is with the Switch set to N.C. and the Jumpers set to NC. In this mode
the Relays are normally open and normally closed when operated.
Alternative settings are:-
With the Switch set to N.C. and the Jumpers set to NO, the Relays are closed going open.
With the Switch set to N.O. and the Jumpers set to NC, the Relays are closed going open.
With the Switch set to N.O. and the Jumpers set to NO, the Relays are open going closed.
Setting AR401-RO16B DIP Switches
ID 2
ID 3
ID 4
ID 5
ID 1
ID Number
Jumper J10 set to
Normally Open
Jumper J9 set to
Normally Closed
(Default Setting)
Jumper J10 set to
Normally Open
Jumper J9 set to
Normally Closed
(Default Setting)
Relay
Baud Rate N/A
N.O.
N.C.
N.C. = Switch 8 on
N.O. = Switch 8 off