24 February, 2010
RBH Access Technologies Inc.
14 of
26
TB61_PC-
100 for AxiomV™
DSC Alarm Panel Interface
The PC100 is used as a bridge between the Axiom Access Control System and
the IT-100 interface for the DSC alarm panel. To achieve this functionality the
PC100 emulates eight Safesuite
™ keypads and up to eight sequentially
addressed IOC‟s.
Axiom
Safesuite™
Address
DSC
Partition
Address
101
1
102
2
103
3
104
4
105
5
106
6
107
7
108
8
Whenever a partition is armed or disarmed by the DSC system the
corresponding Safesuite™ keypad will display the status. For example if keypad
number 102 reports that it is disarmed it really means that Partition 2 has been
disarmed. For the virtual keypads there will be no zones assigned, instead the
virtual IOC‟s will reflect the input status. Using Links to arm or disarm a group of
inputs allows the virtual IOC‟s the capability of reporting the DSC panel‟s inputs.
Using an input group assigned to a virtual keypad allows the software the
capability of assigning any number of inputs to each virtual keypad.
To truly reflect the input status of the DSC Alarm Panel four links must be added
to the keypad configuration.
Axiom
Link
DSC
Type
Link Function
Disarm
Disarm
Disarm all inputs except for Fire and 24 hour types of
inputs.
Home
Stay
Arm all inputs except for interior, entry and exit zones.
Evening Night
Arm all inputs except for interior night zones.
Away
Away
Arm all inputs.
In order to synchronize the DSC Alarm Panel with the Axiom Access Control the
Paradox inputs are mapped to virtual IOC-16 using the first eight panels on the
point number table