Optional PVC vent system installation instructions supplement

3

O

Figure 2 

PVC Vent Vertical Adaptor

PVC VENT ADAPTOR INSTALLATION

 

Improper installation of the PVC vent adaptor can 
cause pooling of corrosive condensate and result in 
premature failure of the vent adaptor voiding the 
manufacturer’s warranty!

Remove the right rear jacket panel to gain access to the Fusion’s 
economizer cabinet. With the PVC vent adaptor positioned at the 
rear of the unit carefully insert the manual reset high limit through the 
fl ue pipe opening in the rear cabinet panel. Mount the high limit to 
the economizer bracket as shown in Figure 3.

 

Do not kink or damage the high limit capillary tube or the 
limit may be ruined voiding the manufacturer’s 
warranty!

Place the small end of the vent adaptor through the vent pipe opening 
in the rear cabinet panel. Position the vent adaptor so the high limit 
switch capillary is at the top of the adaptor, Figures 1 and 2. 

Summary of Contents for Futera Fusion FTF-PVCVO-2

Page 1: ... damage Do not use the boiler during construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be operated with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation wit...

Page 2: ... The return water temperature entering the Futera FusionusingthePVCventingoptionmustnotexceed 155 F Higher return water temperatures will result in a reduction of the firing rate The PVC vent adapter Figures 1 and 2 comes fitted with a flue temperature sensor and flue temperature high limit switch This systemprovidesredundantover temperatureprotectionforthePVC ventsystem Thefluetemperaturesensorco...

Page 3: ...access to the Fusion s economizer cabinet With the PVC vent adaptor positioned at the rearoftheunitcarefullyinsertthemanualresethighlimitthroughthe flue pipe opening in the rear cabinet panel Mount the high limit to the economizer bracket as shown in Figure 3 Donotkinkordamagethehighlimitcapillarytubeorthe limit may be ruined voiding the manufacturer s warranty Placethesmallendoftheventadaptorthro...

Page 4: ...nding a chimney liner gas vent special gas vent or plastic piping installed within a masonry chimney shall not be used to vent another appliance The PVC vent adapter has been engineered to directly accept PVC ventpipe Theinternalgasketintheventadaptorwillformagasand watertightseal Nogluesorsealantsarerequiredatthisconnection Slide the required horizontal length of PVC pipe into the vent adaptor an...

Page 5: ...e Do not store them near heat sparks or flames Keep containers closed when not in use Wear imperviousclothingwhilehandling Donotsmoke eat ordrinkwhilehandlingprimers cleanersandcements Wash thoroughly after handling and before eating Wear eye protection when handling The harmful vapors can be absorbed through the skin and may irritate eyes and skin If inhaled get fresh air and seek medical attenti...

Page 6: ...rd screeninsertsasshownbelow Theminimumdistancefromthe wall must be maintained as shown in the Figures below Figure 4 Horizontal PVC TEE Terminal Figure 5 Horizontal PVC 45 Elbow Terminal Figure 6 Horizontal PVC 90 Elbow Terminal Figure 7 Horizontal PVC Coupling Terminal 10 Min 1 4 SS Bird Screen In Opening 8 Min 1 4 SS Bird Screen In Openings 8 Min 1 4 SS Bird Screen In Openings 10 Min 1 4 SS Bir...

Page 7: ...ertical PVC Terminal TheinputoftheunitmustbesetperTable2ornuisanceshutdowns may occur under strong wind conditions Table 1 Turn Down vs Combustion Air Source When vented vertically the vent and air intake systems should be terminated using standard 45 and 90 PVC Elbow fittings with a 1 4 in stainless steel bird screen insert as shown below TherestoftheapplicableCombustionAir VentilationandVenting ...