16
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
Figure 10 – Outdoor Venting
Figure 11 – Multiple Outdoor Units
Figure 9 – Vertical Venting using a Masonry Chimney
OUTDOOR VENTING
When installed outdoors the Futera III must be fitted with
the factory supplied outdoor hood, air intake adapter with
filter and exhaust terminal, see Figure 7A. Multiple units
must be spaced per Figure 7B.
The boiler/heater must be at least
2 ft
, .62 m from any
door, window or gravity air inlet into any building and at
least
3 ft
, 1 m from any overhang unless local codes dictate
differently.
Avoid locations where wind deflection off of adjacent walls,
buildings or shrubbery might cause a downdraft. The
unit(s) shouild be located at least
3 ft
, 1 m from structures.
Outdoor installations are not recommended in areas where
the danger of snow blockage exists.
CAUTION: Do not place the boiler/water heater in a
location that would subject it to runoff from adjacent
buildings or damage may occur voiding the warranty!
DISCHARGE VENT
GAS TRAIN COWLING
AIR INLET
UNDER COWLING
RIOM-60 REV. A
2 FT
(0.62 M)
3 FT
(1 M)