background image

4

FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS

WARNING: Never operate the Futera II in an 

environment subjected to a negative pressure 

unless it is Direct Vented.  Failure to comply with 

this warning can result in excessive levels of 

carbon monoxide causing severe personal injury 

or death!

All Air From Inside The Building

 

If the Futera II is to be located in a confined space, the 
minimum clearances listed in Table 1 must be maintained 
between it and any combustible construction. When 
installed in a confined space 

without the intake air 

option,

 Figures 7, 8 and 9, two permanent openings 

communicating with an additional room(s) are required. The  
combined volume of these spaces must have sufficient 
volume to meet the criteria for an unconfined space. The 
total air requirements of all gas utilization equipment, 
fireplaces, wood stoves or any type of exhaust fan must  
be considered when making this determination. Each 
opening must have a minimum free area of 

1 in

2

/1000 Btu/ 

hr

,  2200 mm

2

/kW based on the total input rating of ALL  

gas utilization equipment in the confined area. Each 
opening must be no less than 

100 in

2

64,516 mm

2

 in size. 

The upper opening must be within 

12 in

305 mm of, but  

not less than 

3 in

76 mm from, the top of the enclosure. 

The bottom opening must be within 

12 in

305 mm of, but  

not less than 

3 in

,  76 mm from, the bottom of the 

enclosure.

All Air From Outside The Building

 

When installed in a confined space 

without utilizing the 

intake air option

 two permanent openings communicating 

directly with, or by ducts to, the outdoors or spaces that 
freely communicate with the outdoors must be present. The 
upper opening must be within 

12 in

305 mm of, but not 

less than 

3 in

76 mm from, the top of the enclosure. The 

bottom opening must be within 

12 in

305 mm of, but not 

less than 

3 in

76 mm from, the bottom of the enclosure.

Where directly communicating with the outdoors  
or communicating with the outdoors through vertical  
ducts, each opening shall have a minimum free area of 

 

1 in

2

/4000 Btu/hr

,  550 mm

2

/kW of the total input rating  

of all of the equipment in the enclosure.

Where communicating with the outdoors through horizontal 
ducts, each opening shall have a minimum free area of  

1 in

2

/2000 Btu/hr

1100 mm

2

/kW of the total input rating  

of all of the equipment in the enclosure. 

When ducts are used, they must have the same cross-
sectional area as the free area of the opening to which 
they connect.

When calculating the free area necessary to meet the 
make-up air requirements of the enclosure, consideration 
must be given to the blockage effects of louvers, grills and  
screens. Screens must have a minimum mesh size of  

1/4 in

6.4 mm. If the free area through a louver or grill is 

not known, ducts should be sized per Table 2.

Table 2 – Make-up Air Louver Sizing

Required Cross Sectional Area  

 Input 

1/4 in

 6.4 mm  75% Free Area  

25% Free Area

 (MBH) 

  Wire Screen 

 Metal Louvers  

Wooden Louvers     

    

in

2

 

cm

in

2

 

cm

in

2

 

cm

2

   500 

125

  

 806 

167

  1077 

  

500

     3226

   750 

187

  1206 

250

  1613 

  

750

     4839

 1000 

250

  1613 

333

  2148 

1000

     6452

 1250 

313

  2019 

416

  2684 

1250

     8065

 1500 

375

  2419 

500

  3226 

1500

     9677

 1750 

437

  2819 

583

  3761 

1750

  11,290

 1950 

486

  3135 

649

  4187 

1950

  12,580

Canadian installations must comply with CSA B149.1 when 

air supply is provided by natural air flow from the outdoors 
for  natural draft, partial fan-assisted, fan-assisted, or 
power draft-assisted burners, there shall be a permanent 

air supply opening(s) having a cross-sectional area of not 
less than 

1 in

2

 per

 

7,000 Btuh

 (310 mm

2

 per kW) up to 

and including

 

1 million Btuh, 

plus

 1 in

2

 per 14,000 Btuh

 

(155 mm

2

 per kW) 

in excess of

 

1 million Btuh

Intake Air Option – General Guidelines

 

This configuration provides combustion air directly to the 
boiler/water heater’s air intake using a dedicated pipe when 
using the direct vent option. The RBI air intake adapter 
must be fitted to the blower inlet. Combustion air can be 
drawn in horizontally through the same outside wall which 
terminates the exhaust gases or vertically through the roof, 
see Figures 2, 3, 4, 5 & 6.

WARNING: Common intake air systems may be 

used provided the common duct is sized properly 

and an intake combustion air damper is installed 

in the intake air pipe of each heater. Improper 

installation can result in excessive levels of carbon 

monoxide which can cause severe personal injury 

or death!

All joints in metal intake air systems must be secured using 
corrosion resistant fasteners and sealed using a suitable 
Silicone caulk. If PVC or CPVC is used, the joints must be  
cleaned with a suitable solvent and connected using a 
solvent based PVC cement. 

The combustion air system 

MUST be supported by the building structure not the 

boiler/water heater.

CAUTION: A combustion air damper interlocked with 

the unit should be installed in the intake air pipe when 

the infiltration of subfreezing air could occur, otherwise 

the unit could freeze up voiding the warranty!

Intake Air Option – Vertical Guidelines

 

The maximum equivalent length for the vertical intake air 
pipe is 

60 ft

18.3 m. Each 90° elbow and the intake air 

terminal are equal to 

10 linear ft

3.1 m of pipe.

An approved, nonrestrictive intake air terminal must be 
used. The intake air terminal must terminate as shown in 
Figure 5. The penetration point in the roof must be properly 
flashed and sealed.

Summary of Contents for FUTERA II 1000

Page 1: ...uction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be op...

Page 2: ...as Fired Low Pressure Steam and Hot Water Boilers ANSI Z21 56 CSA 4 7 Gas Fired Pool Heaters Canada Only Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160...

Page 3: ...er heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure see GENERAL VENTING GUIDELINES 6 NEVER place this boiler water heater...

Page 4: ...st be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of 1 4 in 6 4 mm If the free area through a louver or grill is not known ducts should be sized p...

Page 5: ...the horizontal combustion air pipe on installations that used the Direct Vent option is 60 ft 18 3 m The maximum equivalent length for the horizontal combustion air pipe on installations that use the...

Page 6: ...61 cm from the center line of the terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter re...

Page 7: ...3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 4 ft 1 2 m below or to side of opening 1 ft 300 mm above opening C Clearance to permanently closed window D Vertical clearance...

Page 8: ...or balcony is fully open on a minimum of two sides beneath the floor NOTES 1 In accordance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z...

Page 9: ...meters gas meters regulators and relief equipment and not less than 7 ft 2 1 m from any adjacent public walkway The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air in...

Page 10: ...10 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 1 Air Intake Vertical or Thru Wall Figure 2 Venting Thru Wall Vertical...

Page 11: ...gle or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wal...

Page 12: ...AND OPERATION INSTRUCTIONS Figure 5 Vertical Air Intake and Venting for Direct Vent System Figure 6 Combination Direct Vent Systems 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1 2 FT 1 7 m 1 5 FT...

Page 13: ...venter for the boiler water heater see Table 4 Follow the power venter manufacturer s installation instructions Table 4 Power Venter Sizes VERTICAL CHIMNEY VENT NEGATIVE PRESSURE CATEGORY I The Futer...

Page 14: ...ingle wall vent connection with at least 3 corrosion resistant sheet metal screws Always provide a minimum clearance of 6 in 152 mm between single wall vent pipe and any combustible materials Type B1...

Page 15: ...15 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 8 Vertical Venting with a Metal Chimney System...

Page 16: ...r window or gravity air inlet into any building and at least 3 ft 1 m from any overhang unless local codes dictate differently Avoid locations where wind deflection off of adjacent walls buildings or...

Page 17: ...marche Suivre les instructions d allumage R gler le thermostat de fa on que l appareil fonctionne de fa on continue e Test for spillage at the draft hood relief opening after 5 minutes of main burner...

Page 18: ...water mix that prevents foaming Air entrapped within foam significantly decreases heat transfer and can result in damage to the heat exchanger Products such as DOWFROST DOWTHERM UCARTHERM or an equiva...

Page 19: ...4 C The adjustable pump delay turns the pump on each time the burner fires and runs the pump for 6 to 600 seconds after the call for heat is satisfied CAUTION A temperature rise outside of the range...

Page 20: ...econdary systems In order to prevent boiler s short cycling the system flow must be equal to or higher than the boiler s local flow Low Return Water Temperatures To prevent the problems associated wit...

Reviews: