152
Ref.
Parameter’s description
Range
Factory
settings
Single burner
(mod. 199 )
Burner 1 (Master)
(mod. 399, 500, 750
and 1000
Burner 2 to 4
(mod. 399, 500,
750 and 1000
Column for
custom.
values
3001
Burner logic address
0 = No cascade,
1 = Burner 1 (Master),
2 to 4 = Burner 2 to 4 (slave
burners)
2
1
1
2 to 4
3002 Fan speed range
0 to 4
0
199=0
399=0
500=2
750=2
1000=2
399=0
500=2
750=2
1000=2
3003 Display units
C = °C and bar units;
F = °F and PSI units;
F
F
F
F
3004 Water pressure sensor
0 = Disabled; 1 = Enabled; 2
= N/A; 3 = N/A
1
1
1
0
3005
Burner flapper valve
0 = Disabled; 4 = Enabled; 8
= N/A; 12 = N/A;
4
0
4
4
3006
Water flow sensor
0 = Disabled; 16 = N/A; 32 =
N/A; 48 = Enabled
48
48
48
48
3007
Condensate blocked
drain detector
EnAb = Enabled; dISA =
Disabled
Enab
Enab
Enab
dISA
3008
Flue gas detector
SEnS = Sensor; StCH =
Switch
SEnS
SEnS
SEnS
SEnS
3009 Outdoor thermistor
type
10 = 10kohms; 12 =
12kohms;
10
10
10
10
3010 Other thermistor type
10 = 10kohms; 12 =
12kohms;
10
10
10
10
3011
Pump MODE
0 = Local pump; 1 = N/A; 2 =
N/A; 3 = N/A;
0
0
0
0
3012 DHW mode
0 = no DHW; 1 = DHW store
with sensor; 2 = DHW store
with thermostat; 3 = N/A; 4 =
N/A; 5 = N/A
0
0
0
0
3013 Reset Err 115
EnAb = Enabled; dISA =
Disabled
Enab
Enab
Enab
Enab
3015
Reset curve design:
Maximum heating
supply temperature
(This parameter is
overruled by 3017
parameter)
68°F to 194°F
179°F
N/A
N/A
N/A
3016
Reset curve design:
Minimum heating
supply temperature
68°F to 194°F
68°F
N/A
N/A
N/A
3017 Maximum supply
temperature (This
parameter overrule
3015 parameter)
68°F to 194°F
179°F
179°F
179°F
179°F
3018 Minimum supply
temperature
68°F to 194°F
89°F
89°F
89°F
89°F
3020
Type of water flow
sensor
0 = N/A; 1 = DN8; 2 = DN 10;
3 = DN 15; 4 = DN 20; 5 =
DN 25
4
4
4
4
20 - FACTORY MENU