IDENTIFICATION DATA
Print name of start-up technician .................................................................................................. , date .............................................
Installer Name ........................................................................................................
Company ................................................................................................ Phone number .................................................................
Heater’s serial number ...................................................................................... Model ............................................................
Street ................................................................................................. City ..........................................
State .............................................. Zip ......................................... Site altitude above see level .......................... ft
DOCUMENTATION
Is the installation manual present at site? Yes No Are all manual information well understood by the heater owner? Yes No
GENERAL INSTALLATION
Are all requirements in terms of clearances from combustible materials be met? Yes No
Is the temperature and pressure relief valve properly sized and installed in accordance with the ANSI/ASME BPVC section IV? Yes No
Is the heater properly grounded? Yes No Is a general main electrical switch installed near the heater? Yes No
Are all requirements in terms of gas supply be met? Yes No Type of gas: Natural gas LP gas
LWCO (or any safety devices downstream the appliance) intervention stops all burners sending unit in Loc 29? Yes No
Is a filter properly sized and installed in the water inlet (water return) pipe? Yes No
Water hardness ......................... ppm
Water flow readed on parameter 1062 ........................ GPM multiply by the quantity of burners .......................... GPM (total water flow on appliance).
Is this last matching the requirements in terms of prevention of scaling (see manual)? Yes No
Static/Dynamic Gas Inlet Pressure = .................... / .................... W.C.
VENTING
Vent and combustion air: Combustion air from room Direct vent
Are all requirements in terms of ventilation of the equipment room be met? Yes No
Material used in venting system: Stainless steel PVC CPVC
Polypropylene
Venting pipe: diameter .................... inch , length ....................... equivalent feet.
Material used in air inlet pipe (if any): Stainless steel PVC CPVC
Polypropylene
Air inlet pipe: diameter .................... inch , length ....................... equivalent feet.
Are any draw venting present (such as extractors, barometric dampers, blast dampers or draft inducers)? Yes No
Are all requirements in terms of flue exhaust and air intake be met? Yes No
Are all requirments in terms of positioning of the flue exhaust and air intake terminals be met? Yes No
Is the flue exhaust pipe properly glued and sealed tight to the heater exhaust adapter? Yes No
COMBUSTION ANALISATION
Room Temp.
HIGH FIRE
LOW FIRE
...................... °F
CO
2
(%)
(1)
O
2
(%)
(1)
CO (0% O
2
)
(4)
NO
X
(ppm)
(2)
Tf (°F)
(3)
CO
2
(%)
(1)
O
2
(%)
(1)
CO (0% O
2
)
(4)
NO
X
(ppm)
(2)
Burner 1 (Master)
Burner 2
Burner 3
Burner 4
(1) compare Installation Manual for range/limits (2) compare local codes for limis (3) flue gas temperature must be less than return tempe 45°F.
(4) less than 150 ppm (natural gas) or 250 ppm (LP gas)
If you answered “No” to any question describe the reason:
.....................................................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................................................
Information must be sent to info@cosmogas.com in order to ensure warranty consideration.