99
16 - USE
Loc 19
Internal software error
Replace the power control board
Loc 20
Flame lost three times
Control: that the ionisation current is at a value over 60
(see parameter 1008)
Control: that the fumes exhaust must be protected with a
wind-proof grid
If the ionisation current is not over 60, the CO2 must be checked (see
chapter 14.8) and restore the correct value. Check the ionisation electrode
and replace it if necessary. Check the integrity of the ionisation current
electric circuit cables.
If the fumes exhaust is placed in a vertical wall it must be protected with
a wind-proof grid. If the fumes exhaust is positioned on the roof, make
sure that it is not in an area of reflux and that any windproof chimney pot
is really efficient.
Loc 21
Internal software error
Replace the power control board
Loc 22
Internal software error
Replace the power control board
Loc 23
Internal software error
Replace the power control board
Loc 24
Internal software error
Replace the power control board
Loc 25
Gas valve circuit
(When this error happens to
burner 1 (MASTER) stops all
other burners)
a - Check High limit temperature switch
b - Check High limit flue temperature fuse
WARNING!!!
If the high limit temperature
fuse melt, before any replacement, it is mandatory to
contact the appliance manufacturer to prevent any
permanent damages to the heat exchanger. Failure to
comply with this requirement can result in excessive
levels of carbon monoxide which can result in severe
personal injury or death!
Loc 26
Internal software error
Replace the power control board
Loc 27
Flame present with closed gas
valve
Replace the gas valve
Loc 28
Flame present with closed gas
valve
Replace the gas valve
Loc 29
Interlock input
(When this error happens to
burner 1 (MASTER) stops all
other burners)
a - Check LWCO connection
b - Check flue blocked pressure switch
a - If LWCO intervenes, try to reset it
b - Check if flue gas line is free from any blockage
Loc 30
Internal software error
Replace the power control board
Loc 31
Five times flame lost during one
demand
a) Check detection electrode;
b) Check for any obstruction on air inlet / flue exhaust
sytem
c) Check for any air inlet contamination from combustion
gas (Eg. flue exhaust terminal too much near air inlet
terminal)
a) Try to replace detection electrode
b) Remove any obstruction
c) Remove the cause of the air inlet contamination
Loc 32
Internal software error
Replace the power control board
Loc 33
Internal software error
Replace the power control board
Loc 34
Internal software error
Replace the power control board
Loc 35
Internal software error
Replace the power control board
Loc 36
Internal software error
Replace the power control board
Loc 37
Internal software error
Replace the power control board
Loc 38
flue gas sensor does not increase a - Check flue gas sensor match Section 16.10
b - Check if flue gas sensor (parameter 1006) increases its
temperature when burner is on
a - If it does not match, it must be replaced
b - If temperature does not increase, replace the flue gas sensor or the
control board