During the design stage, the installation of the following components in
the water supply line must be contemplated.
-
Shutoff
valve: for the hydraulic insulation of the heat exchanger
from the plant during maintenance.
-
Vibration
damper: dampers the vibration that can transmits to
the plant.
-
Pressure
gauge
(with stop valve): indicates the water pressure
in the inlet line.
-
Thermometer: indicates the water temperature in the inlet line.
-
Air
vent:
removes the air from the inlet line.
-
Pipe’s draining valve: drains the water from the plant. To be
used also for connecting an external pump for the chemical
wash.
-
Gauze
filter: separates the impurities from the water.
Install the following components in the water outlet line.
-
Water
flow
meter: measures the water flow in the plant.
-
Pipe’s draining valve: drains the water from the plant. To be
used also for connecting an external pump for the chemical
wash.
-
Air
vent:
removes the air from the outlet line.
-
Thermometer: indicates the water temperature in the outlet line.
-
Pressure
gauge
(with stop valve): indicates the water pressure
in the outlet line.
-
Vibration
damper: dampers the vibration that can transmits to
the plant.
-
Calibration
valve: calibrates the water flow.
-
Shutoff
valve: for the hydraulic insulation of the heat exchanger
from the plant during maintenance.
Install an expansion tanks with safety valve in the heat exchanger
circuit.
Its size must be designed and implemented according to the applicable
laws.