background image

I N S T A L L A T I O N

8371/8372

Surface MiniMag

®

 Electromagnetic Locks

1.  Mount the electromagnetic lock to the door frame as outlined 

on the installation template included with the product. 

NOTE:  During installation of the armature plate to the door it is 

essential that the armature plate remains movable. The armature 

plate must be allowed to pivot on the center-mounting bolt to allow 

proper alignment with the magnet surface. If the plate is not aligned 

with the magnet surface, the lock may lose holding force or not 

lock at all. 

The head of the armature mounting bolt ships with a rubber washer 

affixed to it. This washer should project slightly beyond the surface 

of the armature plate. This is to allow the washer to expand when 

power is removed and break the air vacuum between the plate 

and the magnet surface. If this washer is removed or trimmed the 

lock will appear to have some holding force even when power is 

removed.

 

 

For added safety, thread locking compound has been provided for 

the armature plate bolt and the four captive electromagnetic lock 

mounting screws.

WARNING: Improper installation, maintenance, inspection or 

usage of the product or any related accessories or parts may 
cause the electromagnetic lock, armature plate and associated 
hardware to disengage and fall, causing serious bodily injury 
and property damage. Rutherford Controls Int’l Inc. and/or 
Rutherford Controls Int’l Corp. will not be liable to the installer, 
purchaser, end user or anyone else for damage or injury to person 
or property due to improper installation, care, storage, handling, 
maintenance, inspection, abuse, misuse or act of God or nature 
involving this product or any related accessories or parts.

2.  Route the power supply wire through door frame and into 

magnet housing. Connecting wire should be of sufficient gauge 

for the lock being installed and the distance being run. (See table 

on page 6.)

© 2015 RUTHERFORD CONTROLS INT’L | A DORMA GROUP COMPANY

WWW.RUTHERFORDCONTROLS.COM • PHONE: 1.800.265.6630 • FAX: 1.800.482.9795 • E-MAIL: SALES@RUTHERFORDCONTROLS.COM

IS8371/72

PCN15010

R10/15GR-2

In or Out... we make it Easy!

®

Instructions

Pre-Installation Instructions 

1.   This product must be installed according to all applicable 

building and life safety codes. 

2.   Due to the variety of mounting configurations available with 

this product, a survey and assessment of the physical area 

in which the product will be installed must be performed. 

3.   The door frame must be inspected and deemed structurally 

sound prior to installation of the electromagnetic lock. The 

structural integrity of the mounting surfaces must be strong 

enough to meet or exceed the holding force of the product. 

4.   The product must be protected from potential damage due 

to intruders or tampering. 

5.   The product should be installed in a location that will not 

hinder or create a potential safety hazard to authorized 

personnel accessing the protected area. 

6.   Because electromagnetic locks are used in a variety of 

applications and different door frame configurations, an 

experienced installer with knowledge of this product must 

make a determination of the optimal mounting method for 

this specific application. 

7.   The components, hardware, installation instructions and 

mounting template included with this product are intended 

for use on outswinging doors. 

8.   Do not install this product on the exterior of buildings.

9.  Do not use as a doorstop. This will void warranty. 

10.  Separate accessories not included with this product must  

be used in the following applications: 

 

   •  Inswinging doors 

 

   •  Narrow head jamb situations or center-hung doors 

 

   •  Wherever there is insufficient space on the door   

     frame header to mount the lock 

 

   •  Glass or Herculite doors that do not have a door frame 

 

   •  Hollow metal or wood frames where the door stop is  

     not thick enough to allow the product to be installed 

 

   •  Wherever an obstruction in the door prevents    

     installation of the armature plate at a proper height  

   •  Doors that do not permit the armature plate to be  

     mounted low enough to meet the magnet surface 

 

Refer to the Product Accessories Guide section of 

the Installation Instructions for further information. 

Accessories may impact holding force.

11.  Installation of this product should be done by an 

experienced installer with knowledge of this product. 

NOTE: It is highly recommended that thread locking compound 

be applied to all screws during installation to reduce chance of 

screws loosening over extended time.

PLEASE DELIVER ALL INSTALLATION INSTRUCTIONS TO  

THE END-USER UPON COMPLETION OF THE INSTALLATION.

Summary of Contents for 8371

Page 1: ...t must be installed according to all applicable building and life safety codes 2 Due to the variety of mounting configurations available with this product a survey and assessment of the physical area in which the product will be installed must be performed 3 The door frame must be inspected and deemed structurally sound prior to installation of the electromagnetic lock The structural integrity of ...

Page 2: ...he desired manner Magnet power from Power Supply 12 24VDC input Ground Jumper 12VDC Jumper 24VDC preset Power Input Requirements MODEL 12VDC 24VDC 8371 0 52A 0 26A 8372 1 04A 0 52A 2 x BLUE LEADS Normally Open FOR MODELS WITH OPTIONAL DSS contacts are rated 0 20A 12VDC and 0 12A 24VDC shown with Door Open Wiring For Unmonitored or DSS Sensor Models 12 24 12 G B R LED R B G HR VDC C NC NO G B R LED...

Page 3: ...unting bracket 8371 Lock Dimensions 1 D x 1 7 8 W x 9 3 8 L 25 x 48 x 238mm 8372 Lock Dimensions 1 D x 1 7 8 W x 18 3 4 L 25x 48 x 476mm Armature Plate Dimensions 1 2 D x 1 1 2 W x 7 1 4 L 13 x 38 x 185mm Electrical Voltage 12VDC or 24VDC Current Max 0 52A at 12VDC each lock on 8372 model Max 0 26A at 24VDC each lock on 8372 model SCS Output Relay SPDT relay Contacts rated at 1 0A 24VDC DSS Reed S...

Page 4: ... 4 thick glass doors Used to provide extra mounting space in a hollow metal or wood frame where the door stop of the frame is not thick enough to allow a lock to be installed Available in several different heights and widths For use when an obstruction in the door prevents the installation of the armature plate at a proper height If the armature plate needs to be lowered then a spacer bar can be u...

Page 5: ...two separate categories for use in both the United States and Canada Auxiliary Lock The GWXT fire listing qualifies these for use with UL Classified fire doors maximum 4 in width and 8 in height The 8371 and 8320 are rated up to and including 1 hr Special Locking Arrangement Component Additionally these products are qualified components for the purpose of locking outward swinging exit doors agains...

Page 6: ... Wire Run ft Load Current 24V 1 4A 1 2A 3 4A 1A 1 1 4A 1 1 2A 2A 3A 100 24 20 18 18 16 16 14 12 150 22 18 16 16 14 14 12 10 200 20 18 16 14 14 12 12 10 250 18 16 14 14 12 12 12 10 300 18 16 14 12 12 12 10 400 18 14 12 12 10 10 500 16 14 12 10 10 750 14 12 10 10 1000 14 10 10 1500 12 10 Total One Way Length of Wire Run ft Load Current 12V 1 4A 1 2A 3 4A 1A 1 1 4A 1 1 2A 2A 3A 100 20 18 16 14 14 12 ...

Reviews: