background image

Description

The PDM-4 and PDM-8 board distributes a DC source into 4 or 8 outputs. The output volt-

age and total current available is determined by the input supply. When installed into a 

power supply, service time can be greatly reduced by the output indicator LED’s. If an out-

put fuse is blown the accompanying LED will be off. Simply identifying the device 

connected to this output will allow for a problem to be quickly corrected. In addition to 

short circuit protection the input terminals also have a surge protector that can absorb a 

1500 Watt spike or surge to protect connected devices.

Features

•  Converts a single input to 4 or 8 separately protected outputs

•   Separate RED power indicator LED for each output.

•   Reverse polarity protected.

Installation Instructions 

(See Fig. 1 and 2) 

1)  Mount the distribution board in a suitable location as required.

2)  Connect power to input terminals, (-) is negative and (+) is positive.

  Observe proper polarity

3)  Connect devices to be powered to output CH terminals. Observe proper polarity.

4)  Apply power to input terminals and test all connected devices.

Note:

 

 Unit is to be powered from RCI 10 Series power supply or a UL listed power supply 

 

 Maximum torque of 7in*lb for black input and output terminals

 

 Check end product install instructions for conditions of use