11
5.
SPECIFICATION
(Note: all figures are typical values)
Supply Voltage
Output regulation
12 to 36V dc universal polarity
1µA/V
Loop Resistance
(Max)
(Min)
Output regulation
50
(12V) to 1200
(36V). See Note 1 below
See Note 2 below
2µA/100
Excitation
0.5V rms. 5kHz sinusoidal at 4mA max.
(minimum impedance of transducer = 130 ohm)
Amplifier: Input Signal Range
Gain
Input Impedance
30mV to 4V
2.5 to 333 (20mA equated to 10V)
100K ohm
Zero Range
±8mA
Linearity
0.05%
Bandwidth
Filter ON
250Hz flat
25Hz
Noise
Filter ON
50µA peak-peak
15µA peak-peak
Zero Temperature Coefficient
Gain Temperature Coefficient
0.005% FS/°C
0.015% FS/°C
Maximum Output Overload
45mA
EMC Performance
When subjected to radiated electromagnetic energy
(as EN61000-4-3) an additional error can occur at
certain spot frequencies:
Field Strength
Typical Max. Error
30V/m
0.5mA
3V/m
0.25mA
Operating Temperature
-20 to 85°C (to 100°C possible)
Dimensions
125 x 80 x 57mm (4.7 x 3.2 x 2.1 inches)
Weight
550g (1.2lb)
Seal
To IP65
Gland Cable Diameter
3 to 6.5mm (0.12 to 0.25 inches)
Note 1
The maximum allowable total external circuit resistance is calculated from:
R max = 50(Vs
– 11)
Note 2
Where the supply voltage is higher than 28 volts
and
the ambient
temperature higher than 25°C, then a minimum value of loop resistance is
required:
R min = (Vs
– 28)(t – 25)
Where Vs = supply voltage (volts) and t = ambient temperature (°C)
E.g. at 36 volts supply and 85°C ambient, the value of RL must be between
480 ohms and 1200 ohms.