START-UP AND TESTING -
AVVIAMENTO E COLLAUDO
3.1
INFLOW FAN SETTING ON VENTILATION MODE
| SET VENTILATORE IMMISSIONE IN RINNOVO
Mode
1
2
3
XX =
Mo
de
+
-
UIRn
UIRn
40
40
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
VENTIL
ATION
VENTILAZ.
WINTER/INVERNO
ESTA
TE/SUMMER
SEASON
STA
GIONE
DEHUMIDIF
.
DEUMIDIF
.
INTEGR
ATION
INTEGRAZ.
RENE
WAL
RINNOVO
Consenso rinnovo
Renewal consent
Non scendere a portate inferiori a 650 m
3
/h d’aria in
quanto l’unità DA 701 potrebbe attivare allarmi con blocco
macchina a riarmo manuale.
Non salire a portate superiori a 850 m
3
/h d’aria in
quanto si creano problemi di scarico della condensa.
Do not use air flow rates inferior to 650 m³/h because
the unit DA 701 will activate alarm block with manual reset.
Do not use air flow rates higher than 850 m³/h because
it will affect the condensate drainage.