53
TECHNIC
AL D
AT
A
D
ATI TECNICI
Types of measurement -
Rilievi effettuati
FRESH AIR VENTILATION MODE
- MODALITA’ RINNOVO ARIA
Supply Fan
Ventilatore
Immissione
Exhaust Fan
Ventilatore
Espulsione
Flowrate
setting
Set Portata
Aria
Supplyt Fan
revolutions
Giri Ventilatore
Immissione
Exhaust Fan
revolutions
Giri Ventilatore
Espulsione
A
B
C
D
E
(m
3
/h)
(min
-1
)
(min
-1
)
(dB
A
)
ON
ON
100
725
689
44
59
43
44
-
ON
ON
150
951
891
51
68
49
50
-
ON
ON
200
1185
1103
53
69
55
57
-
ON
ON
250
1455
1351
61
81
60
62
-
ON
ON
300
1688
1574
62
82
64
66
-
ON
ON
350
1890
1769
68
84
67
68
-
ON
ON
400
2167
1975
72
84
71
72
-
AIR RECIRCULATION MODE
- MODALITA’ RICIRCOLO ARIA
Supply Fan
Ventilatore
Immissione
Exhaust Fan
Ventilatore
Espulsione
Flowrate
setting
Set Portata
Aria
Supplyt Fan
revolutions
Giri Ventilatore
Immissione
Exhaust Fan
revolutions
Giri Ventilatore
Espulsione
A
B
C
D
E
(m
3
/h)
(min
-1
)
(min
-1
)
(dB
A
)
ON
OFF
300
1460
-
64
-
-
-
67
ON
OFF
400
1866
-
71
-
-
-
72
ON
OFF
500
2329
-
77
-
-
-
78
NOTE
:
• Nella tabella sovrastante sono stati volutamente inseriti i giri
del ventilatore in quanto trattandosi di ventilatori a portata
costante il dato di portata d’aria risulta insufficiente per
comprenderne il livello di rumorosità.
• L’unità è posta in un ambiente chiuso riverberante senza
alcuna schermatura del rumore radiante della carrozzeria, nè
canali d’aria (bocca libera)
• Il numero massimo di giri del ventilatore si attesta intorno ai
3200 giri/min.
• E’ possibile avere un numero di giri elevato anche in presenza di
portate basse, ciò dipende fortemente dal dimensionamento
dei canali d’aria e in minima parte dallo stato di pulizia dei
filtri e condotti.
NOTES:
• In the above-mentioned chart the revolutions of the fan have
been intentionally included because the appliance contains
fans with constant volume and the sole air flow rate value is not
enough to understand their noise level.
• The appliance has been situated in a closed reverberating room
without shielding the noise of the casing and without using any
ductwork (from open outlet)
• The maximum number of revolutions for the fan is about 3200
per minute.
• The fan may have a large number of revolutions even with low
flow rate. This depends on the sizing of the air ductwork and
partially on the integrity of filters and ducts.