OPERATION & CONTROL
Air Handling Unit
Temovex Blue 4
REC Indovent AB, Box 37, SE-431 21 Mölndal, Sweden
|
+46-31-675500
|
www.rec-indovent.se
11
3. In/Outputs
In this menu it is possible to check the status of every input and output.
It is also possible to calibrate the sensors in this menu.
Analog inputs status.
All current temperatures are displayed here.
The room temperature is only displayed if room control is
configured.
Freeze temperature is only displayed if water heater is
configured.
UAI3 displays the adjusted setpoint if TG-R4 is chosen as
option.
Digital inputs status.
”Not active” means that the input is not in use (nothing is
configured to the input).
“On” means 24V on the input and the function that is
configured to the input is active.
“Off” means 0V on the input and the function that is
configured to the input is not active.
The alarm inputs can have status Ok or Alarm.
Analog outputs status.
Current voltage on the output is displayed.
Digital outputs status.
”On” means that the output is active and “Off”
consequently that the output is not active.
Calibrating the temperature sensors.
The sensors
’ values may be adjusted up or down. (Set an
offset value). For example, the old common thermometer
could be synchronized with the AHU temp. State the
difference here and they will show the same.
|
}
|
|
|
|
}
~
€
~
€
DI4 SA fan :Ok
↑
DI5 EA fan :Ok
DI6 Not active :Off
DI7 Overheat p:Ok
↓
Analog inputs
►Digital inputs
Analog outputs
Digital outputs
DI1 AHU On/Off :On
DI2 Not active :Off
DI3 Not active :Off
↓
~
€
DI8 FilterAla:Ok
↑
|
|
}
AO1 SA fan: 5.0 V
AO2 EA fan: 5.0 V
AO3 Heater: 10.0 V
AO4 Chiller : 0.0 V
Analog inputs
Digital inputs
►Analog outputs
Digital outputs
~
€
|
|
|
}
~
€
DO1 BP opening :On
DO2 BP closing :Off
DO3 PWM heat :Off
DO4 Sum alarms :Off
↓
Digital inputs
Analog outputs
►Digital outputs
Calibrate sensors
DO5 CP heater :Off
↑
DO6 KAVK :Off
DO7 ULS :On
~
€
|
~
€
|
}
|
UAI1: 24.7ºC K: 0.0
↑
UAI2: NaN ºC K: 0.0
UAI3: ºC K:
UAI4: ºC K:
AI1: 18.3ºC K: 0.0
AI2: 24.6ºC K: 0.0
AI3: 23.2ºC K: 0.0
AI4: 13.3ºC K: 0.0
↓
Digital inputs
Analog outputs
Digital outputs
►Calibrate sensors
~
€
~
€
|
|
}
AI1 OB temp 10.0ºC
AI2 SA temp 20.0ºC
AI3 EA temp 21.3ºC
AI4 EXT temp 14.0ºC
↓
UAI1 Room t. 10.0ºC
↑
UAI2 Freeze t. 12.0ºC
UAI3 TG-R4. 0.5 ºC
UAI4 Aux 2 NaN ºC
►Analog inputs
Digital inputs
Analog outputs
Digital outputs
Continued from In/outputs, page
Fel! Bokmärket är inte definierat.
Summary of Contents for G10125
Page 19: ...19 Notes...