OPERATION & CONTROL
Air Handling Unit
Temovex Blue 4
REC Indovent AB, Box 37, SE-431 21 Mölndal, Sweden
|
+46-31-675500
|
www.rec-indovent.se
13
5. Alarm
All current alarms and the status can be seen by pressing the red button.
In this menu alarms can be acknowledged, blocked or unblocked (allow alarm).
There are 2 types of alarms: A and C alarms. A-alarms do not disappear until they have been fixed and
acknowledged. C-alarms are internal alarms and will disappear automatically as soon as the alarm reason has
disappeared.
Some faults cause immediate stop of the unit, as continued operation would be dangerous.
An acknowledged alarm that has not yet been dealt with remains on the menu as
Acknowledged.
It disappears
from the menu when the fault has been dealt with.
It is possible to block an alarm and continue to run the unit.
Note!
Do not do this unless you really know what you
are doing, since it could be dangerous and in worst case damage both unit and property.
Alarm history
The last 21 alarms are displayed. You can see when the alarm went off, when it was acknowledged and/or
returned and so on. In this menu, it is not possible to acknowledge or block any alarms.
List of alarms. (abbreviations
– see page 43)
A-alarm
C-alarm
Sensor error OD temp
Sensor error SA temp
Sensor error EA temp
Sensor error EXT temp
Sensor error RM temp
Sensor error FRP temp
Freeze P alarm
Supply fan
failure
Exhaust fan failure
El. heat. overheated
Filter alarm
Filter guard
Fire damper alarm
Fire alarm
SA controller man.
SA fan manual
EA fan manual
Heater manual
By-pass manual
Chiller manual
ULS (Outdoor air damper) manual
KAVK (Condensation boiler) manual
P1-heating manual
P1-cooling manual
Int. battery failure
Warning temperature deviati
|
~
€
|
Sensor error OD
28 Feb 15:20 Klass:A
↓
Any menu
Back to earlier menu
EL.heat. overheated
↑
28 Feb 14:34 Klass:A
EL.heat. overheated
►Acknowledge
Block
OK
~
€
28 Feb 15:20 A
↑
EL.heat. overheated
Activated
↓
Continued from Alarm history, page
Fel! Bokmärket är inte definierat.
28 Feb 13:50 A
↑
Sensor error OD
Acknowledge
↓
|
}