DESIGN & TECHNICAL NFORMATION 

 

Air Handling Unit 

Temovex Blue 4 

REC Indovent AB, Box 37, SE-431 21 Mölndal, Sweden 

|  

+46-31-675500  

|

  www.rec-indovent.se 

 

 

Product description 

 

Temovex Blue 4 is an air handling unit (AHU) fitted 
in a cabinet.  The unit is designed for the ventilation 
of homes, offices, nurseries and other small 
premises. 
The Temovex unit should be installed in a heated 
room, such as a scullery, laundry or similar. 
 
The standard Temovex unit consists of a 
counterflow heat exchanger, 2 fans, 2 filters, after-
heater, by-pass damper and a control system. 
 

 

Positioning guide 

 
1.   Casing 

2.   Filter, exhaust  

  air (behind  
  inspection door) 

3.   By-pass damper 

4.   Fan, exhaust air 
      (backside) 

5.   Fan, supply air 

6.   Counterflow heat  
 

exchanger 

7.   Filter supply air    
      (behind 2.) 

8.   Elevator device 

9.   Adjustable feet 

10. Condensate  
 

drain 

11.Control panel 

12.After-heater 

 

 

 
1. Casing 

Inside is the unit made of EPP (Expanded 
PolyPropylene). The outside casing is made of 
galvanised sheet metal with 30mm insulation. As a 
standard, the side panels and the front are white 
(powder paint). The front door has a magnetic strip 
which keeps the door closed. The unit top has 
sleeve connections made of EPP, where all ducts 
are connected. 

 
 

2. Exhaust air filter 

G4, bag (art. No. G10125) 
 

 
3. By-pass damper 

The Temovex AHU has an automatic by-pass 
damper which makes the air by-pass the heat 
exchanger whenever heat recovery is not 
necessary.  The by-pass setting is adjusted on the 
control panel. 

 
 

4. Exhaust air fan 

The unit has low-energy fan of EC type with 
integrated overheating. 

 
 
5. Supply air fan 

The same type as exhaust air fan (see point 4). 
 
 

6. Heat exchanger 

The heat exchanger is a standard highly efficient 
counterflow heat exchanger from Recair. The heat 
exchanger is made of very thinny, pleated plastic 
sheets and and the supply air and exhaust air sides 
are completely sealed from each other. This is 
important in order to avoid odours and other 
contaminants from old air seeping through to fresh 
air. The heat exchanger has no moving parts, which 
eliminates wear. 
 

 

7. Supply air filter 

F7, bag (art. No. G10126) 

 
 

8. Elevator device 

The elevator device must unfasten to make it 
possible to take out the heat exchanger for cleaning. 
(See chapter "Maintenance & service"). 
 

 

9. Adjustable feet 

The cabinet has adjustable rubber feet.

 

 
 
10. Condensate drain 

The Temovex unit is fitted with a condensate drain 
at the bottom of the unit.  This should be connected 
to a drain or fed to a floor drain.

 

 
 

11. Control panel 

All settings for fan speed, after-heating, by-pass etc

.  

are made via the control panel and the AHU's 
integrated control system. 
If you have added optional parts to your Temovex 
AHU, these functions, too, are set via the control 
panel. 

 
 
12. After-heater 

Temovex Blue 4 is fitted with an electric after-
heater, 0.9 kW.   
As an optional extra, a reinforced electric after-
heater, 1,8 kW, or a water coil (two different sizes) 
for waterborne heating is offered.  The heater is 
integrated in the unit and settings are made via the 
control panel. 
In the case of a water coil, the water connections 
are at the top of the unit, dimension DN12

The Temovex Blue 4 with water coil includes a two-
way valve and valve motor in the consignment from 
REC. 
 

 

11 

10 

12 
 

Summary of Contents for G10125

Page 1: ...ndovent AB Box 37 SE 431 21 M lndal Sweden 46 31 675500 www rec indovent se 1 User manual 1 6 1 01 DESIGN TECHNICAL INFORMATION OPERATION CONTROL MAINTENANCE SERVICE Exhaust air filter article No G101...

Page 2: ...erat Main menu Version Language Address 1 Temperature 8 Temperatures ECO adjustment Control function 2 Mode 9 10 Fan control Timer adjustments Date time and summer wintertime Activate timer Time sched...

Page 3: ...with integrated overheating 5 Supply air fan The same type as exhaust air fan see point 4 6 Heat exchanger The heat exchanger is a standard highly efficient counterflow heat exchanger from Recair The...

Page 4: ...tor heat recovery By pass EVBV After heater electricity water GT1 Sensor supply air temperature GT11 Sensor outdoor air temperature TFR Filter outdoor air FFR Filter exhaust air TF Fan supply air FF F...

Page 5: ...nded heater 900 W Output water coil small standard 1500 W 1 Output water coil extended 2800 W 1 Voltage Frequenzy input 230 V 50 Hz 230 V 50 Hz Fuse 10 A 10 A Filter supply air exhaust air Bag F7 Bag...

Page 6: ...ere it is possible to change some parameters Steady You are now in change position The menu system The AHU s settings and status can be studied by scrolling the menu screens Some parameters and settin...

Page 7: ...p Version Shows current program version and the serial number of the electronics Present date and time is shown and can be changed here Language choice Choose Swedish English or Polish Address Shows t...

Page 8: ...18 and 22 degrees ECO adjust is activated when ECO is enabled Control function What is shown in the temperature menu depends on the selected control function There are four control functions to choose...

Page 9: ...4 01 01 01 01 5 01 01 01 01 6 01 01 01 01 Holiday mm dd 7 01 01 01 01 8 01 01 01 01 9 01 01 01 01 Holiday mm dd 10 01 01 01 01 11 01 01 01 01 12 01 01 01 01 Holiday mm dd 13 01 01 01 01 14 01 01 01 01...

Page 10: ...switch to minimum flow but gradually increase to normal flow when there is need for higher or lower temperature ECO adjust gives a temperature range around the setpoint and neither heat nor cool is en...

Page 11: ...output is not active Calibrating the temperature sensors The sensors values may be adjusted up or down Set an offset value For example the old common thermometer could be synchronized with the AHU tem...

Page 12: ...een 0 100 The actual position of the by pass damper is displayed in the menu Digital outputs All configured digital output signals such as ULS KAVK CP etc can be assigned Auto On or Off or a similar w...

Page 13: ...s and in worst case damage both unit and property Alarm history The last 21 alarms are displayed You can see when the alarm went off when it was acknowledged and or returned and so on In this menu it...

Page 14: ...ing has been saved the standard settings apply All settings except date and time will be loaded 7 Authorization This is where an authorized technician can log in to adjust the system and if necessary...

Page 15: ...with serial data RS485 to the ventilation unit Remote panel With display art nr Q101299 Remote panel With display is the most advanced remote panel It has a temperature sensor that could be used as ro...

Page 16: ...han AUTO The unit may run at a fan speed between minimum and normal or between normal and boost flow due to boosting or safe mode The symbol fan speed shows actual fan mode as follow Fan speed zero no...

Page 17: ...the power Open the unit door Remove both upper and lower cover Unfasten the elevator device at the bottom of the front side of the unit so that the heat exchanger package is released from the topunit...

Page 18: ...the air diffusers Take down the diffuser Use a vacuum cleaner or duster to clean the inner part of the duct as far as you can reach Refit the diffuser making sure the setting is not changed Checking...

Page 19: ...19 Notes...