223553 / 9160625310
2018-05-24·BA00·III·en·04
Engineering
11
Transmitter power supply
N-132...IL
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
6
Engineering
6.1
Maximum Ambient Temperatures
Series N-132 devices can be used across a wide temperature range.
The maximum permissible ambient temperatures vary based on the device version
and installation condition.
6.2
Power Dissipation
The max. power dissipation in rated operation (output: 20 mA; auxiliary power: 24 V DC;
load = 250 W) is specified in the "Technical Data" chapter. In practice, not all devices are
operated at a full load. As a result, project engineering is usually performed at an average
power dissipation of 70 % (P
70%
).
Ventilation
Without air circulation
Installation
Single device
DIN rail
Mounting position
any
vertical
horizontal
06289E00
06877E00
06875E00
2 channels
70 °C
45 °C
50 °C
Ventilation
With air circulation
Installation
Single device
DIN rail
Mounting position
any
vertical
horizontal
06289E00
06877E00
06875E00
2 channels
70 °C
60 °C
60 °C
Max. power dissipation
70 % power dissipation
2 channels
2.8 W
1.96 W