RM-216 CB.10 Easy Line Documentation
RDN 10000088
15
07.07.2016
11 Technical specifications
Application
Data
Supply voltages
230 V AC ±10%
110 V ... 120 V AC ±10%
26 V … 28 V DC*
Signal inputs
24 V DC, operate ensuring isolation
Signal output
Relay outputs, max. 2 A, 250 V
or 1 A, 30 V DC
Control outputs for valves
For valves with a rated voltage of 24 V DC,
can be expanded to 128 outputs,
Output power in pulse mode 42 Watt
Outputs for expansion
modules
Supply voltage and pulse wires to the expansion modules
Fuses
230 V:
T 0.4 A, 250 V, 5 x 20 mm
110 V:
T 0.8 A, 250 V, 5 x 20 mm
Extra low voltage: Fusing via PTC resistor
Temperature range
-20°C to +60°C
Degree of protection
Casing IP-66 / NEMA 4
Dimensions
See chapter 3 “Assembly”
Weight
approx. 0.8 kg
Installation height
max. 3000 m above M.S.L.
*
The unit can be operated with a supply voltage of 24 V DC, if no expansion modules are connected and if the electric cables to
the solenoid valves are shorter than 3 meters long.
Disclaimer
The contents of this documentation has been verified for correctness and completeness. Nevertheless, errors can not be excluded
so that we cannot guarantee the correctness of this information. Subject to alterations at any time.