5.10 Parameter description and explanation of function
Parameter B0 “Display language”
The display texts can be shown in different national languages. The text output is in German when the
system is delivered.
B0 =
Text in display, line 3
Meaning
0
0 D - Deutsch
Text output German
1
1 GB - English
Text output English
2
2 F - Francais
Text output French
Parameter block C0-C4 "Service operating hours counter"
Parameter C0 "Service operating hours counter"
The service operating hours counter can be activated or deactivated with parameter C0. The parameter
value is factory-set to 0 (= inactive).
C0 =
Text in display, line 3
Meaning
0
0 inactive
The operating hours counter is deactivated. The parameters C1
through C3 are not displayed.
1
1 act.w/o mess.
The operating hours counter is activated but without external messag-
es.
2
2 act.w. mess.
The operating hours counter is activated, with external service or
alarm messages.
Parameter C1 “Operating hours counter mode”
The operating hours counter mode can be set with parameter C1.
C1 =
Text in display, line 3
Meaning
0
0 Power on
The counter counts when mains voltage is present.
1
1 DP > 200 Pa
The counter counts when the differential pressure is > 200 Pa.
2
2 Cleaning on
The counter counts when cleaning is activated.
3
3 DP /Clean on
The counter counts when the differential pressure is > 200 Pa or
cleaning is activated.
Parameter C2 "Service alarm"
The service alarm switch point can be set with parameter C2. It is factory-set to 3000 hours. Once the
counter reaches the set value the yellow LED is activated and signals a present warning to the operator.
On the display, the service alarm message „Operating hours" appears.
Parameter C3 "Service alarm reset"
A maintenance technician can reset the operating hours counter for the service alarm to 0 with parameter
C3. The present service alarm message is cleared and the yellow service LED switched off.