Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104
28
14.07.2020
Parameter block E0-E8 “Cleaning control functions”
Parameter E0 “Cleaning control functions”
Cleaning control functions can be activated or deactivated with parameter E0. The parameter value is factory-
set to 0 (= active).
E0 =
Text in display, line 3
Meaning
0
0
The cleaning control functions are inactive
1
1
The cleaning control functions are active via RMV-XX control
(I/O module RM-V 8
2
or RM-V 16
2
).
2
2
The cleaning control functions are active via RMV-XX-SMD control
(I/O module RM-V 6/X
1
or RM-V 8.10
2
/ RM-V 16.10
2
).
1
only types RM-310 C Plug and Play and RM-310 CT Plug and Play
2
only types RM-310 C and RM-310 CT
Parameter E1 "Interval 1"
The period between two successive cleaning pulses can be set in 0.1-second increments via parameter
E1.
Parameter E2 "Interval mode"
The parameter is factory-set to 0 and is therefore not active. With parameter setting E2 = 1 all intervals
are multiplied with factor 10,
except
with active interval controller.
Parameter E3 "Interval 2"
The period between two successive cleaning pulses can be set in 0.1-second increments via parameter
E3 during downtime and forced cleaning.
Parameter E5 "Pulse time A" (cleaning valve)
Valve pulse time A can be set in 10-millisecond increments via parameter E5.
Parameter E6 "Pulse time mode A"
The parameter is factory-set to 0 and is therefore not active. With the parameter setting E6 =1 the pulse
time of the cleaning valves is multiplied with factor 10.
Parameter E8 "Forced cleaning time"
The parameter is factory-set to 0 and is therefore not active. The forced cleaning time is set via parameter
E8. If cleaning is in the stopped state, a complete cycle is always cleaned after the set forced cleaning
time has elapsed.
Parameter E9 “Downtime cycles”
The last run cycles can be set with parameter E9. Interval 2 is always active during downtime.
Parameter EA “Number of valves”
The number of dedusting valves connected to the filter system can be set with parameter EA.
Parameter EB “Number of I/O modules”
The number of I/O modules (RM-V 8 or RM-V 16) connected to the filter system can be set with parame-
ter EB.
A communication alarm is triggered if the number of the I/O modules detected at the controller
start differs from the settings.
Parameter EC “Cleaning skip range”
In the delivery state the valves are selected in direct succession (1, 2, 3, 4 .../ skip range = 1). Depending
on the filter arrangement cleaning in a different order may be useful (for example: 1, 4, 7, 10 … / skip
range = 3). The product discharge can be regulated this way. A cleaning skip range from 1 to 120 can be
set with parameter EC. However, the value cannot be chosen greater than half the value of the number of
valves set (parameter EA).