8.3 Operating messages 2 to 4
Operating messages 2 to 4 are the currently valid parameter values. The effective differential pressure is
displayed only when parameter D0 "
Δ
p
control" is set to value 1 (active).
Display
Meaning
Operating message 2
DP-Min Al. #### Pa
DP-Max Al. #### Pa
DP Pre-Al. #### Pa
DP filter #### Pa
Row 2
Row 3
Row 3
Row 4
####
set value Δ
p
-Min Alarm
####
set value Δ
p
-Max Alarm
####
set value Δ
p
-pre-alarm*
####
currently measured differential pressure of filter
*
The operating message is displayed only when the parameter D9
Δ
p pre-
alarm is set to a value greater than 0 (alternating at 3-second cycle with
the value set for
Δ
p Max. alarm).
Operating message 3
DP-Start 1200 Pa
DP-Stop 900 Pa
DP-Filter #### Pa
Row 2
Row 3
Row 4
Parameter "Starting cleaning"
Parameter "Stopping cleaning"
####
currently measured differential pressure of filter
Operating message 4
Interv.t. ##,# s
Pulse t. ### ms
Downtime ## cyc.
DP-Filter #### Pa
Row 2
Row 3
Row 4
Row 4
##,#
effective value of interval
###
effective value of pulse time
##
effective value of downtime cycles*
####
currently measured differential pressure of filter
*
The operating message is displayed only when downtime is active. If
downtime is not active, the currently measured differential pressure of the
filter is displayed instead.
8.4 Operating message 5 – only with active service operating hours counter
Display
Meaning
Next service
Row 1 Next service
* #### h
Row 2
####
Time to next service
The asterisk symbol at the beginning of the row flashes when
the service operating hours counter is active.
Operating hours
Row 3 Elapsed general operating hours (mains on)
###### h
Row 4
######