17-FAULTS/CAUSES/SOLUTIONS

ANOMALY

POSSIBLE CAUSES

SOLUTIONS

Pellets accumulate in the brazier, the 

glass of the door gets dirty and the 

flame is weak.

Insufficient combustion air.

Clean the brazier and check that all the 

holes are clear. Perform a general cleaning 

of the combustion chamber and the smoke 

duct. Check that the entry of air is not 

obstructed.

Damp or unsuitable pellets.

Change the type of pellets.

Faulty smoke extractor motor.

Check the motor and replace it, if necessary.

The smoke extractor motor does not 

work.

No electrical supply to the stove.

Check the mains voltage and the 

protection fuse.

The motor is faulty.

Check the motor and capacitor and replace 

them, if necessary.

Defective motherboard.

Replace the electronic board.

The control panel is broken.

Replace the control panel.

The convection air fan never stops.

Faulty or malfunctioning temperature 

control probe.

Check the probe and replace it, if necessary.

In the automatic position, the stove 

always runs at full power.

Thermostat is set to minimum.

Reset the temperature of the thermostat.

The room thermostat is in the maximum 

position.

Reset the temperature of the thermostat.

Malfunctioning temperature probe.

Check the probe and replace it if necessary.

Faulty or malfunctioning control panel.

Check the panel and replace it, if necessary.

The product does not start.

No power supply.

Check that the plug is inserted and the 

main switch is in the “I” position.

Pellet sensor has seized up.

Check the recipe parameters.

Blown fuse.

Replace the fuse.

Pressure switch broken (lockout indicated). Insufficient pressure of water in stove.

Clogged smoke outlet or smoke duct.

Clean the smoke outlet and/or the smoke 

duct.

Noisy air fan even though it is set to 

minimum

High set flame causes ventilation increase Lower set flame from Adjustments menu

Summary of Contents for LOTO Multiair

Page 1: ...INSTALLATION GUIDE GB PELLET STOVE LOTO Multiair PART 2 OPERATION AND CLEANING Instructions in English...

Page 2: ...I 10 FIRST START UP 3 11 CONTROL PANEL 5 12 MENU ENTRIES AND OPERATION 6 13 SAFETY DEVICES 14 14 ALARMS 15 15 RECOMMENDATIONS FOR SAFE USE 20 16 CLEANING 21 17 FAULTS CAUSES SOLUTIONS 31 18 COMFORT AI...

Page 3: ...After connecting the power cable to the back of the product turn the switch at the back to position I To turn the stove on or off press button 1 on the control panel The display on the panel will be O...

Page 4: ...eandsmellofpaint Do not stand close to the boiler and ventilate the room as described The smell of paint will disappear after about an hour of operation however it is not harmful in any case The produ...

Page 5: ...served Reproduction prohibited KEY 1 Stove switch on switch off 2 Scrolling down through the programming menu 3 Menu 4 Scrolling up the programming menu 5 Decrease set temperature programming function...

Page 6: ...dashes Example TIMER 1Timer 1 program active TIMER 1 4Timer 1 and 4 programs active TIMER 1 2 3 4 5 6 All timer programs active EXAMPLE OF PROGRAMMING With the stove on or off access the MENU scroll...

Page 7: ...another program if the stove is already on the start has no effect while OFF turns off the stove When the stove is on and the timer is active pressing the OFF key turns off the stove the stove then re...

Page 8: ...to the set values when the room temperature drops below the set threshold PLEASE NOTE The point to the right of the room temperature on the control panel display indicates the half degrees e g 23 C i...

Page 9: ...scroll through and select Settings Press menu to confirm Use the arrow keys to scroll through and select language Press menu to confirm Use the keys to select the required language IT EN DE FR ES NL...

Page 10: ...e and time settings see paragraphs 8 f and 8 g respectively ECO stop T can be adjusted to ensure correct operation in the various environments in which the stove can be installed and to avoid constant...

Page 11: ...ease thesmokeandashextractionspeed Thischangeresolvesallthepotentialproblemsrelatedtopelletsclogginginthebrazieranddeposits forming at the bottom of the brazier itself caused by poor quality fuel or f...

Page 12: ...eeper function as follows Press the menu key Use the arrow keys to scroll through and select Settings Press menu to confirm Use the arrow keys to scroll through and select Chimney sweeper function Pre...

Page 13: ...ure it provides Connect the cables coming from the external thermostat to terminal 14 on the board on the stove Enable the external thermostat factory settings OFF as follows Press the menu key Scroll...

Page 14: ...reached TEMPORARY POWER CUT When a power cut is less than 10 the stove returns to its previous operating state if it is more it executes a cooling re ignition cycle FAILED START UP If during ignition...

Page 15: ...fuel to minimum SETTINGS menu pellet recipe If the alarm persists contact the service centre Check whether the room fan is working correctly A04 Smoke overtemperature Reduce the load of pellets SETTIN...

Page 16: ...by activating the smoke extractor at minimum speed for 10 then proceed to the next step 2 Restore the stove to the operating condition prior to the blackout During phase 1 the panel shows ON BLACK OUT...

Page 17: ...to The flue clogging The presence of a foreign body in the flue birds nests clogged grates etc Wind coming through the flue because it is unprotected or the installation was wall mounted or required...

Page 18: ...in Active System products RPM 30 50 in NON Active System products The percentage variation affects all the power values 1 to 5 proportionally and as a percentage The percentage variation does not aff...

Page 19: ...moke temperature PLEASENOTETheindicatednegativepressurereadingsmaydifferby 1Pabasedonfluegastemperature Likewise fluegastemperature may differ by 10 C based on fuel quality or appliance cleanliness Ch...

Page 20: ...e product is installed in compliance with standards in force Furthermore it is of the utmost importance to respect the following simple rules Every time the brazier is removed for cleaning it must alw...

Page 21: ...es little maintenance if used with certified good quality pellets DAILY ORWEEKLY CLEANING PERFORMED BYTHE USER Brazier cleaning Before ignition always clean the brazier T and remove any ash or incrust...

Page 22: ...e holes and the grate on the bottom If good quality pellets are used you will normally only need to use a brush to restore the optimal operating conditions of the component Cleaning the ash box To cle...

Page 23: ...ng the motor body and the internal sensor It is recommended to check that the filter is clean every 15 20 days If needed remove fluff or the material that has deposited on it Inspection and cleaning a...

Page 24: ...mandatory in order to facilitate the general removal of all combustion residue before it becomes very difficult to remove it due to moisture compacting it over time ATTENTION Itisobligatorytohaveanau...

Page 25: ...ur t screws and remove cap H Loosen the four screws y remove the plate n and the gasket o Use the nozzle of a vacuum cleaner to remove any ash and soot that may have built up in the lower exchanger sm...

Page 26: ...estion The first step is to take out the internal cast iron Open the firebox door lift the T cast irons slightly and tilt them towards you to take them out of their place and remove them Then pull out...

Page 27: ...use a stiff rod or a bottle brush to scrape the walls of the firebox see arrow to make the ash fall into the lower compartment Use a stiff rod or a bottle brush to scrape the walls of the firebox see...

Page 28: ...28 16 CLEANING Use a vacuum cleaner nozzle to vacuum up any remaining ash and dust on the exchanger see arrow Then thoroughly clean the lower exchanger replace any gaskets if needed and reassemble...

Page 29: ...t the operation ATTENTION The frequency with which the smoke outlet system is cleaned depends on the use of the boiler and the type of installation We recommend relying on an authorised service centre...

Page 30: ...rised and qualified technician CHECKINGTHE INTERNAL COMPONENTS ATTENTION The internal electromechanical components must only be checked by qualified personnel whose technical expertise includescombust...

Page 31: ...restore the thermostat until the lockout is off and switch the product back on If the problem persists contactTechnical Assistance The door is not closed properly or the gaskets are worn Closethedoora...

Page 32: ...onvection air fan never stops Faulty or malfunctioning temperature control probe Checktheprobeandreplaceit ifnecessary In the automatic position the stove always runs at full power Thermostat is set t...

Page 33: ...uction prohibited ANOMALY POSSIBLE CAUSES SOLUTIONS No increase in temperature with stove in operation Incorrect combustion adjustment Check recipe Set flame 1 setting level too low Increase power fro...

Page 34: ...ROOM FAN FAN 2 12 AUGER 13 SMOKE SENSOR 14 EXTERNALTHERMOSTAT CONNECTION TERMINAL 15 ROOMTEMPERATURE PROBE 16 17 18 SMOKE EXTRACTOR FAN REVOLUTION CONTROL 19 20 21 22 REAR ROOM FAN FAN 3 23 24 25 CON...

Page 35: ......

Page 36: ...21 06 2017 REV 0 8901717800 Via La Croce n 8 33074Vigonovo di Fontanafredda PN ITALY T l phone 39 0434 997200 Internet www red365 it e mail info red365 it...

Reviews: