A
A
B
A
C
MIN.1,5 m
MIN.1,5 m
MIN.1,5 m
MIN.0,3 m
14
2-INSTALLATION
EXTERNAL AIR INLET
It is mandatory to provide an adequate external air inlet that supplies the combustion air required for the product to work properly. The
flow of air between the outside and the installation room may be direct, through an inlet in an external wall of the room (preferable
solution see Figure 9 a); or indirect, via air intake from adjoining rooms and connecting permanently with the installation room (see Figure
9 b). Adjoining areas may not include sleeping areas, garages or general areas with a fire hazard. During installation one must check the
minimum clearances required for air intake from outside. Take into account the presence of doors and windows that could interfere with
the proper flow of air to the stove (see diagram below).
The air inlet must have a minimum net total area of 80 cm2: the surface must be increased accordingly if there are other active generators
(for example: electric fan for stale air extraction, hood, other stoves, etc.), which could cause a depression in the room. Make sure that,
with all appliances on, the pressure drop between the room and the outside does not exceed the value of 4 Pa (also for Oyster appliances
if the combustion air has not been suitably ducted outside). If necessary increase the intake section of the air inlet, which must be made
at floor level and always protected with a bird-proof outer protection grid and in such a way that it cannot be obstructed by any object.
It is possible to connect the air required for
combustion directly to the outside air inlet,
with a pipe of at least Ø50mm, with maximum
length of 3 linear metres; each pipe bend shall be
considered equivalent to a linear metre. To attach
the pipe see the back of the stove.
For stoves installed in studio flats, bedrooms and
bathrooms (where allowed), it is mandatory to
connect the combustion air outside. In particular
for sealed stoves the connection must be sealed
in order not to compromise the overall sealed
characteristic of the system.
FIGURE 9 A - DIRECTLY FROM OUTSIDE
FIGURE 10
FIGURE 9 B - INDIRECTLY FROM THE ADJACENT ROOM
A=AIR INLET
B=ROOM TO BE VENTILATED
C=INCREASE OF THE GAP UNDER THE DOOR