CONNECTIONS & CONFIGURATION SWITCH SET-UP FOR VARIOUS SENSOR OUTPUTS

COUNT SWITCH OR ISOLATED TRANSISTOR OUTPUTS

SENSORS WITH CURRENT SINK OUTPUT (NPN O.C.)

[Includes ASTC, LMPC, PSAC, RPGC, (RPGB, RPGH) 

*

, LSC]

SENSORS WITH CURRENT SOURCE OUTPUT (PNP O.C.)

TWO WIRE PROXIMITY SENSORS

OLDER STYLE, SENSORS WITH

A.C. INPUTS FROM TACH.

INPUT FROM CMOS & OTHER

INPUT FROM TTL

-EF OUTPUT

GENERATORS, INVERTERS,

BI-POLAR OUTPUTS

ETC.

RECOMMENDED RULES FOR MAGNETIC PICKUP CONNECTIONS

1. Use 2-wire shielded cable for magnetic pickup signal leads.
2. Never run signal cable in conduit, troughs, or cable bundles with power carrying

conductors.

3. Connect the shield to the common Terminal “4” at the input of the instrument. Do

NOT connect the shield at the pickup end, leave it “open” and insulate the exposed
shield to prevent electrical contact with the frame or case. (Shielded cable, supplied
on most RLC magnetic pickups, has open shield on pickup end.)

INSTALLATION ENVIRONMENT

The unit should be installed in a location that does not exceed the

maximum operating temperature and provides good air circulation. Placing
the unit near devices that generate excessive heat should be avoided.

The bezel should be cleaned only with a soft cloth and neutral soap

product. Do NOT use solvents.

Continuous exposure to direct sunlight may accelerate the aging process of

the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate

the keypad of the unit.

INSTALLATION

PBLR installation information is contained in the LDD bulletin. Refer to

that bulletin for instructions on installing the module.

The unit meets NEMA 4/IP65 requirements for indoor use, when properly

installed. The units are intended to be mounted into an enclosed panel with a
gasket to provide a water-tight seal. Two mounting clips and screws are
provided for easy installation. Consideration should be given to the thickness
of the panel. A panel which is too thin may distort and not provide a water-
tight seal. (Recommended minimum panel thickness is 1/8".)

Cut the panel opening to the specified dimensions. Remove burrs and clean

around the panel opening. Slide the panel gasket over the rear of the unit to
the back of the bezel. Insert the unit into the panel. As depicted in the drawing,
install the screws into the narrow end of the mounting clips.  Thread the
screws into the clips until the pointed end just protrudes through the other
side. Install each of the mounting clips by inserting the wide lip of the clips
into the wide end of the hole, located on either side of the case. Then snap the
clip onto the case.

Tighten the screws evenly to apply uniform compression, thus providing a

water-tight seal. 

CAUTION: Only minimum pressure is required to seal panel.

Do 

NOT

overtighten screws.

Summary of Contents for APLR Series

Page 1: ...die cast bezel which meets NEMA 4 IP65 specifications for wash down and or dust when properly installed Two mounting clips are provided for easy installation The Time Base Rate Indicator uses a 6 digi...

Page 2: ...puts as well as the 5 V and higher logic levels S1 ON MAG PKUP Connects a 0 1 f damping input capacitor from input to common This capacitor is used only with magnetic pickup inputs and serves to filte...

Page 3: ...rom contactors control relays transformers and other noisy components 5 In extremely high EMI environments the use of external EMI suppression devices such as ferrite suppression cores is effective In...

Page 4: ...ure to direct sunlight may accelerate the aging process of the bezel Do not use tools of any kind screwdrivers pens pencils etc to operate the keypad of the unit INSTALLATION PBLR installation informa...

Page 5: ...P switch 2 2 As shown above DIP switches 2 and 4 8 are all set to ON If it is desired to know what the time is in seconds multiply 250 x 0 004 sec 1 sec Note This is the set up for a one second time b...

Page 6: ...128 Needed 6 DIP switch 3 4 Needed 2 DIP switch 2 2 DIP switches 2 3 and 8 are set to ON If the rounding error introduced above is unacceptable the display could be scaled up by a factor of 10 and th...

Page 7: ...7 This page intentionally left blank...

Page 8: ...ty for any affirmation promise or representation with respect to the products The customer agrees to hold Red Lion Controls harmless from defend and indemnify RLC against damages claims and expenses a...

Reviews: