background image

3

HARDWARE INFORMATION

This bulletin contains a variety of information related to the installation and

operation of the Operator Interface supplied. Ideally, you should read this
document thoroughly before attempting to use the equipment. For information
about the software aspects of the terminal, please consult other documentation.

CONTENTS OF PACKAGE

The Operator Interface is supplied in a packaging box containing the

following...

!

The interface terminal itself.

!

A NEMA 4/IP65 rated mounting gasket.

!

A bag containing panel hardware.

!

This hardware bulletin.

!

If any of these items is missing, please contact your supplier

immediately.

POWER SUPPLY REQUIREMENTS

The Operator Interface requires an 11 to 30 VDC power supply rated at 3.0

W unless otherwise stated on the label.

!

The terminal may take as little as 100 mA in certain circumstances, so be

sure that the chosen power supply can operate correctly with this load.
Large switch-mode supplies tend to need a certain minimum load before
they will operate correctly.

In any case, it is very important that the power supply is mounted correctly if

the unit is to operate reliably. A very high proportion of reported problems are
caused by incorrect power supply installation, so please take care to observe the
following points...

!

The power supply must be mounted close to the unit, with usually not

more than 6 feet of cable between the supply and the Operator Interface.
Ideally, as short a length as is possible should be used.

!

The wire used to connect the Operator Interface’s power supply should be

of at least 22 gage wire. If a longer cable run is used, you should use
heavier gage wire. The routing of the cable should be kept away from
large contactors, inverters and other devices which may generate
significant electrical noise.

BATTERY BACKUP ISSUES

The Operator Interface is supplied with a Lithium Battery designed to

maintain the internal memory and real-time clock during power outages.
Assuming the operator interface terminal is powered up for 50% of the time, this
battery should last over 4 years. A “Battery Low” system variable is available
so that the programmer can choose specific action(s) to occur when the battery
voltage drops below its nominal voltage.

It is possible to replace the battery without losing the contents of the Operator

Interface’s memory, but this does not reduce the importance of ensuring that a
copy of the terminal’s configuration is kept readily at hand to allow the terminal
to be re-loaded in the case of mishaps. Please remember that although an image
of the database contents can be uploaded, this file is not editable, so the
importance of keeping a copy on disk cannot be over stressed.

CHANGING THE BATTERY

To change the internal battery, follow these steps...

!

Remove the power and PLC communications connector from the unit.

!

Remove the four screws from the rear-cover and remove the cover.

!

If you wish to avoid losing the terminal’s configuration, reconnect the

power connector and re-apply power. Note that this will require the panel
to be powered-up and, as such, only suitably qualified staff should carry
out this procedure.

!

The battery is located in a holder on the main circuit board. This should

be clearly visible. Remove the battery from its holder.

!

Place the new battery in the holder. The terminal’s power supply can

now be disconnected, if you re-applied power in the step above.

!

Replace the lid, screws and connector by following the above procedure

in reverse. You may like to make a note of the date the battery was
replaced to allow planned maintenance to be carried out.

!

If you did not keep the unit powered-up during battery replacement, hold

down the EXIT and MUTE keys on the keyboard and cycle power.
Release the keys and follow the menu guides to clear the memory. The
unit is now ready for a configuration database to be reloaded.

Please note that the old battery must be disposed of in a manner which

complies with your local waste regulations. Also, the battery must not be
disposed of in fire or in a manner whereby it may be damaged and its contents
come into contact with human skin.

INSTALLATION & CONNECTIONS

The unit meets NEMA 4/IP65 requirements for indoor use, when properly

installed. The units are intended to be mounted into an enclosed panel.

Installation Environment

The unit should be installed in a location that does not exceed the maximum

operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.

Continuous exposure to direct sunlight may accelerate the aging process of

the bezel. The bezel should be cleaned only with a soft cloth and neutral soap
product. Do NOT use solvents.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the

keypad of the unit.

CONNECTING TO A PLC

The Operator Interface is designed to operate with a PLC. A serial

communication connection must be made between the operator interface
terminal and PLC, and the details of this connection vary according to which
PLC is used.

The following section lists the connection details for the PLC to be used .

PLC TYPE 

Details on how to connect to most PLCs are available on request from RLC.

CONNECTING TO AN IBM

®

PC/AT

The Operator Interface is programmed via software running on an IBM

PC/AT or a compatible computer. The connection between the PC/AT and the
operator interface terminal is made via a custom cable provided with the EDICT
Developer’s Kit. The cable is designed for a 9-way serial port. Please contact
your supplier if you require a 25-way version.

PROGRAMMING PORT PIN OUT

The Operator Interface’s programming port is sometimes used to connect

other RS-232 devices, such as printers. The following illustration and table
gives the pin-out of this port to enable such connections to be made.

The above table denotes the pin names of the programming port. When

connecting, the pin name at the programming port is connected to the opposite
of that pin name at the destination device.

MOUNTING INSTRUCTIONS

The Operator Interfaces are designed for through-panel mounting. A

neoprene gasket is provided, to enable sealing to NEMA 4/IP65 specification.
The panel cut-out diagram for the model supplied is provided. All mounting
holes should be drilled for 0.14" (3.5 mm) clearance. Care should be taken to
remove any loose material from the mounting hole to avoid such metal falling
into the Operator Interface itself during installation.

TROUBLESHOOTING

For further technical assistance, contact technical support at the appropriate

company numbers listed. 

Summary of Contents for CL40

Page 1: ...y command motors valves or other actuators not equipped with safeguards To do so can be potentially harmful to persons or equipment in the event of a fault to the unit SPECIFICATIONS 1 POWER REQUIREMENT 11 min to 30 max VDC 3 0 W Power Up Current 3 0 A for 1 msec max Must use a Class 2 or SELV rated power supply 2 DISPLAY 2 lines of 40 characters 0 197 5 mm high liquid crystal display with bright ...

Page 2: ...requirements via a powerful program language For example a program designated Calculate Volume which determines the amount of fluid in a round tank at specific temperatures could be created This program would be triggered to run and display each time the page denoted as Volume Now is requested The ability to customize to your application s specialized needs is easily solved with the user program c...

Page 3: ...it board This should be clearly visible Remove the battery from its holder Place the new battery in the holder The terminal s power supply can now be disconnected if you re applied power in the step above Replace the lid screws and connector by following the above procedure in reverse You may like to make a note of the date the battery was replaced to allow planned maintenance to be carried out If...

Page 4: ...used by its negligence RLC does not warrant any of its software products to be free from error or to be fit for any particular purpose Neither is the software guaranteed to provide operation without interruption The customer s sole remedy in case of failure is the refund of the purchase price of the software The customer in applying the products and software described herein accepts that the produ...

Reviews: