2.06 (52.4)
10.06 (255.6)
6.47
(164.4)
6.7
(171)
(MOUNTING CLIPS INSTALLED)
10.3 (262)
2.97 (76)
Module sold
separately
GRAPHITE™ SERIES
9" Color Touchscreen Operator Interface
Installation Guide
DIMENSIONS In inches (mm)
See the Red Lion website or the enclosed USB thumbdrive
for full user manual, Crimson software and software
manual.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired. Do not use this unit to directly
command motors, valves, or other actuators not equipped with safeguards. To
do so can be potentially harmful to persons or equipment in the event of a fault
to the unit.
ORDERING INFORMATION
DESCRIPTION
PART NUMBER
9" color touch screen, indoor use, 24 VDC powered
G09C0000
9" color touch screen, indoor use, 24 VDC powered,
additional ethernet port
G09C1000
SPECIFICATIONS
POWER
: +24 VDC ±20%
Typical Power HMI only:
13 W
Maximum Power HMI only:
20 W
Available Power for Modules: 25 W
HMI With Module(s):
45 W
Must use a Class 2 circuit according to National Electrical Code (NEC),
NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited
Power Supply (LPS) according to IEC 60950-1 or Limited-energy circuit
according to IEC 61010-1.
Power connection via removable three position terminal block.
ENVIRONMENTAL CONDITIONS
:
Operating Temperature Range: -20 to 60 °C
Storage Temperature Range: -20 to 70 °C
Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g
Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays)
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION:
Risk of electric shock.
Drawing No. LP0908 D
Released 05/15
C
US LISTED
UL
R
IND. CONT. EQ.
34AD
FOR USE IN HAZARDOUS LOCATIONS:
Class I, Division 2, Groups A, B, C, and D
Class II, Division 2, Groups F and G
Class III, Division 2
C
US
UL
R
LISTED
IND.CONT. EQ.
3PWL
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF
OR AREA IS KNOWN TO BE NON-HAZARDOUS.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2
II 3 G Ex ic nA IIC T4 Gc
II 3 D Ex tc IIIC T135°C Dc
DEMKO 14 ATEX 1387X
IECEx UL 15.0035X
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com