MOUNTING INSTRUCTIONS
This operator interface is primarily designed for
through-panel mounting. Four VESA mount tapped
screw-holes (M4 x 0.7, 5 mm deep) are present on the rear
of the panels to allow for stand or wall mounting. Care
should be taken to remove any loose material from the
mounting cut-out to prevent that material from falling into
the operator interface during installation. A gasket is
provided to enable sealing to NEMA 4X/IP66 specification.
Install the twelve mounting clips provided and tighten to 6.0
pound-force inch [96 ounce-force inch] (0.68 N m) evenly
for uniform gasket compression.
Provisions should be made to prohibit the product from
being exposed to UV radiation while in use. Care should be
taken not to rub or buff the touchscreen surface in a way that
might cause the accumulation of static charges.
CONNECTING TO EARTH GROUND
Each operator panel has a chassis ground terminal on the back of the unit.
Your unit should be connected to earth ground (protective earth).
The chassis ground is not connected to signal common of the unit.
Maintaining isolation between earth ground and signal common is not required
to operate your unit. But, other equipment connected to this unit may require
isolation between signal common and earth ground.
To maintain isolation
between signal common and earth ground care must be taken when connections
are made to the unit.
For example, a power supply with isolation between its
signal common and earth ground must be used. Also, plugging in a USB cable
may connect signal common and earth ground.
1
1
USB’s shield may be connected to earth ground at the host. USB’s shield in
turn may also be connected to signal common.
FOOT MAY BE REMOVED
FOR THICKER PANEL
INSTALLATIONS
For hazardous location installation, this device
must be mounted in a suitable ATEX/IECEx
certified end-enclosure with a minimum
ingress protection rating of at least IP66 as
defined in EN/IEC 60529 and used in an environment of
not more than Pollution Degree 2 per EN 60664-1. Must
be wired using Division 2 wiring methods as specified in
article 501-4 (b), 502-4 (b), and 503-3 (b) of the National
Electrical Code, NFPA 70 for installation within the United
States, or as specified in section 19-152 of Canadian
Electrical Code for installation in Canada.
5.832
(148.1)
9.423 (239.3)
4X R.10 (2.5)
MAX.
All tolerances ±.059" (±1.5 mm)
PANEL CUT-OUT
The protective conductor terminal is bonded to conductive
parts of the equipment for safety purposes and must be
connected to an external protective earthing system.
Steps should be taken to eliminate the buildup of
electrostatic charges including but not limited to
connecting to earth ground.
O
peratOr
I
nterface
I
nstallatIOn
1.77
(45)
2.95
(75)
2.95 (75)
1.48 (37.5)
VESA MOUNT (MIS-D 75) DIMENSIONS
CERTIFICATIONS AND COMPLIANCES
:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
ATEX Approved
II 3 G Ex ic nA IIC T4 Gc
II 3 D Ex tc IIIC T135°C Dc
DEMKO 14 ATEX 1387X
EN 60079-0, -11, -15, -31
IECEx Approved
Ex ic nA IIC T4 Gc
Ex tc IIIC T135°C Dc
IECEx UL 15.0035X
IEC 60079-0, -11, -15, -31
UL Listed: File #E302106
UL Hazardous: File #E317425
Type 4X Indoor / IP66 Enclosure rating (Face only) for all models
CONNECTIONS
: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gauge Capacity: One 14 AWG (1.63 mm) solid,
two 18 AWG (1.02 mm) or four 20 AWG (0.81 mm)
CONSTRUCTION
: Cast aluminum enclosure with NEMA 4X/IP66 rating for
indoor use only when correctly fitted with the gasket provided. Installation
Category II, Pollution Degree 2 as defined in IEC 60664-1. These devices
have only been evaluated for low risk of mechanical impact.
WEIGHT
: 3.39 lb. (1.54 Kg)