background image

 

Inside US: +1 (877) 432-9908

Bulletin No. G07-F

Outside US: +1 (717) 767-6511

Drawing No. LP0907

www.redlion.net

Released  2017-03-30 

-1-

Model

 

G07

 ‐ 

Graphite®

 

Series

 

7"

 

Color

 

Touchscreen

 

Operator

 

Interface

 

Terminal

 

Installation

 

Guide

C

US LISTED

UL

R

IND. CONT. EQ.

34AD

FOR USE IN HAZARDOUS LOCATIONS: 

Class I, Division 2, Groups A, B, C, and D 

Class II, Division 2, Groups F and G 

Class III, Division 2
T4

C

US

UL

R

LISTED

IND.CONT. EQ.

3PWL

II 3 G Ex ic nA IIC T4 Gc
II 3 D Ex tc IIIC T135°C Dc
-20°C 

 T

AMB

 

 60°C

DEMKO 14 ATEX 1387X
IECEx UL 15.0035X

See the Red Lion website at www.redlion.net or the 

enclosed USB thumbdrive for full user manual, Crimson® 

software and software manual.

SAFETY

 

SUMMARY

All safety related regulations, local codes and instructions that appear

in the manual or on equipment must be observed to ensure personal
safety and to prevent damage to either the instrument or equipment
connected to it. If equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.

Do not use the controller to directly command motors, valves, or other

actuators not equipped with safeguards. To do so can be potentially
harmful to persons or equipment in the event of a fault to the unit.

ORDERING

 

INFORMATION

SPECIFICATIONS

POWER

Must use a Class 2 circuit according to National Electrical Code

(NEC), NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1
or a Limited Power Supply (LPS) according to IEC/EN 60950-1 or
Limited-energy circuit according to IEC/EN 61010-1.
Power connection via removable three position terminal block.

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range:  -20 to 60 °C, or lowest range among

equipment used in your Graphite system. Consult the user manual

WARNING - EXPLOSION HAZARD - DO NOT D
EQUIPMENT UNLESS POWER HAS BEEN SW
OR AREA IS KNOWN TO BE NON-HAZARDOU

CAUTION: Risk of Danger.

Read complete instructions prior to installation 
and operation of the unit.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 
OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 
DIVISION 2.

DESCRIPTION

PART NUMBER

7" Color Touch Screen, Indoor Use

G07C0000

7" Color Touch Screen, Indoor/Outdoor Use

G07S0000

G07C

G07S

Input Voltage 10V

24V

30V

10V

24V

30V

Typical Power HMI only:

7  W

7  W

8  W

8  W

9  W

9  W

Maximum Power HMI only:

12 W 13 W 14 W 13 W 14 W 15 W

Available Power for Modules:

21 W

21 W

Max Power HMI With Module(s):

33 W 34 W 35 W 34 W 36 W 36 W

(MOUNTING CLIPS INSTALLED)

5.51

(139.9)

7.70 (195.5)

2.00 (50.8)

5.7

(146)

7.9 (202)

2.97 (76)

Module sold

separately

DIMENSIONS

 

In

 

inches

 

(mm)

Reviews: