background image

4.0 S

CALING

 

THE

 M

ETER

3.1  POWER WIRING

DIRECT VOLTMETER READOUT

When the application requires direct voltmeter readout, the Scale Switch 

should remain in the “OFF” position. The Input Range Jumper is set to the 
voltage range being applied. It is possible to select a range higher than being 
applied to get lower resolution. The Decimal Point switches are set to resolution 
of the selected Input Range Jumper.

SCALING VOLTMETER READOUT

In many industrial applications, a voltmeter is required to display a reading 

in terms of PSI, RPM, or some other unit of measure. The signal voltage being 
measured can be generated by a transducer that senses the variations and 
delivers a linear output voltage. To provide the desired readout at the specified 
voltage, the voltmeter must be scaled.

Place the Scale Switch in the “ON” position. This enables the Scale 

Potentiometer which is accessible from the back of the meter. (Enabling the 
Scale Potentiometer does NOT affect the calibration of the meter.) Place the 
Decimal Point Switches to the proper location. To properly set the Input Range 
Jumper, the Division Factor must be determined by first using the below formula. 
After the Division Factor is calculated, use the Division Factor Range Selection 
Chart to choose the proper Input Range Jumper setting. Apply the meter power 
and the voltage signal. Adjust the Scale Potentiometer to the desired value.

This scaling only effects the span. There is no offset scaling. This means that 

only zero voltage can display a value of zero.

DIVISION FACTOR FORMULA:

VT  x  D.D.P.  

=  D.F.

D.R.

WHERE:

 VT 

Maximum 

Transducer 

Output

 

D.D.P  =  Display Decimal Point

 D.F. 

Division 

Factor

 D.R. 

Desired 

Reading

 
 

 

D.D.P.

 

0.000  =  1 

The Display Decimal Point

 

00.00  =  10 

(D.D.P.) is determined by

 

000.0  =  100 

the desired decimal point

 

0000  =  1000 

placement in the readout.

After the Division Factor for the application has been calculated, the proper 

voltage range jumper can be selected. Use the “Division Factor Range Selection 
Chart” to choose the proper jumper setting.

DIVISION FACTOR RANGE SELECTION CHART

 

 

D.F. 

       Use Input Position

        0.1 to 1.2  

       Pos 1: 0-1.999 VDC

       1.2 to 10.5              Pos 2: 0-19.99 
     10.5 to 100.5          Pos 3: 0-199.9 
    100.5 to 1300          Pos 4: 0-300

Note: Only one voltage jumper should be selected. Install the jumper before 

the voltage signal is applied.

EXAMPLE

: A relative humidity transducer delivers a 7.0 VDC voltage at a 

relative humidity of 75%.

D.F. =  VT  x  D.D.P.  =  7.0  x  1000  =  93.3

         D.R.                  75

This Division Factor is between 10.5 and 100.5, therefore jumper position 3  

(199.9 V) is selected. The Scaling Potentiometer is then adjusted for the desired 
readout at a known relative humidity.

1K

9K

90K

900K

0-1.999V

0-19.99V

0-199.9V

0-300V

PROCESS

CIRCUITRY

+VDC

SCALE

POT

S5

S3

S2

S1

+SIGNAL

COMMON

S4

1.9.9.9

6

3.2  INPUT SIGNAL WIRING

Before connecting signal wires, the Input Range Jumper should be verified for proper position. 

PAXLI
Current Signal (self powered) 

Terminal 4: + Amps DC/AC
Terminal 3: - Amps DC/AC

PAXLV
Voltage Signal (self powered)

Terminal 4: + Volts DC/AC
Terminal 3: - Volts DC/AC

3

4

V

-

+

300V MAX.

SIGNAL

COMM

3

4

A

-

+

2A MAX.

COMM

SIGNAL

BLOCK DIAGRAM PAXLV

PAXLV

1

2

AC

AC

115/230

AC Power

Terminal 1: VAC
Terminal 2: VAC

Summary of Contents for PAXLI

Page 1: ...vironmental conditions A DIP switch is used to control the backlight for the units label The meters have a NEMA 4X IP65 sealed bezel and extensive testing of noise effects to CE requirements allowing the meter to provide a tough yet reliable application solution SAFETY SUMMARY All safety related regulations local codes and instructions that appear in the literature or on equipment must be observed...

Page 2: ... the Meter 6 Troubleshooting 7 Calibration 7 TABLE OF CONTENTS ORDERING INFORMATION PAXL 0 I Current Input V Voltage Input 0 A AC Input D DC Input Meter Part Numbers Accessories Part Numbers APSCM100 APSCM010 PAXLBK30 100 Amp DC Current Shunt 10 Amp DC Current Shunt Units Label Kit Accessory APSCM PAXLBK Accessories TYPE PART NUMBERS DESCRIPTION MODEL NO ...

Page 3: ...ARTH 350 volt peak 16 CERTIFICATIONS AND COMPLIANCES SAFETY UL Recognized Component File E179259 UL61010A 1 CSA C22 2 No 61010 1 Recognized to U S and Canadian requirements under the Component Recognition Program of Underwriters Laboratories Inc UL Listed File E137808 UL508 CSA C22 2 No 14 M95 LISTED by Und Lab Inc to U S and Canadian safety standards Type 4X Enclosure rating Face only UL50 IECEE ...

Page 4: ...230 115 REAR TERMINALS FRONT DISPLAY 4 2 0 SETTING THE JUMPERS AND SWITCHES SWITCH FUNCTION 1 Decimal Point 1 000 0 2 Decimal Point 2 00 00 3 Decimal Point 3 0 000 4 Backlight Annunciator for Units Label 5 Enables the Scaling Pot 1 0 INSTALLING THE METER Installation The PAX meets NEMA 4X IP65 requirements when properly installed The unit is intended to be mounted into an enclosed panel Prepare th...

Page 5: ... enclosure which is properly connected to protective earth 2 Never run Signal or Control cables in the same conduit or raceway with AC power lines conductors feeding motors solenoids SCR controls and heaters etc The cables should be run in metal conduit that is properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used in close proxim...

Page 6: ...y zero voltage can display a value of zero DIVISION FACTOR FORMULA VT x D D P D F D R WHERE VT Maximum Transducer Output D D P Display Decimal Point D F Division Factor D R Desired Reading D D P 0 000 1 The Display Decimal Point 00 00 10 D D P is determined by 000 0 100 the desired decimal point 0000 1000 placement in the readout After the Division Factor for the application has been calculated th...

Page 7: ...Scaling to obtain a numerical readout higher than the normal value of the current can also be accomplished in most cases by selecting a lower current range However the maximum current for the range must not be exceeded See Specifications for maximum input currents PROCESS CIRCUITRY VDC S3 S2 S1 S4 COMMON SIGNAL 0 199 9mA 0 19 99mA 1 Ω 9 Ω S5 0 1 999mA 0 199 9µA 90 Ω 900 Ω POT SCALE 1 Ω 0 1 999A 1 ...

Page 8: ...uyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warranties expressed or implied are created with respect to The Company s products except those ex...

Reviews: