20
(2) UPS Output Connection
The output of the UPS is IEC socket-types. Simply plug the load power cord
to the output sockets to complete connection. Use one cord for every 5A
load.
Model No.
Output Socket (pcs)
1K, 1K-KS, 2K, 2K-KS
8 * IEC320 C13
3K, 3K-KS
8 * IEC320 C13 + 1 * C19
The wiring configuration ( 3K-KS only) is shown
as the following procedure:
a) Remove the small cover of the terminal block
b) Use 2.5mm
2
wires for wiring configuration
c) Upon completion of the wiring configuration,
please check whether the wires are securely
affixed
d) Put the small cover back to the rear panel
(3) EPO Connection:
The polarity of EPO is NC (Normally closed) as default setting.
Normally the EPO connector is closed with a wire on the rear panel. Once
the connector is open, the UPS would stop the output until the EPO status is
disabled.
Enable the EPO status Disable the EPO status
( UPS output is OFF )
( normal status )
Connection diagram
Caution:
Do not connect equipment which would overload the UPS system (e.g. laser
printers)