COVER HS Series – User manual
COMEX S.A.
48
Enable or disable bypass mode
–
Possible with icons
(transfer to bypass mode) and
(turn off the bypass mode).
Turn on inverter – touching icon
allows to transfer from bypass mode to inwerter.
Ability to disable power module - To access the power module off from the OFF key on the
module, click the icon
.
Clear history of battery events – touching icon
allows to clear all history according
time of charging, amount of discharge etc.
Clear the history of the use of the pollen filter – touching icon
allows you to delete
the entire story associated with the use of the filter, exchange dates,etc.
Command keys:
Battery test – Touching icon
Allows the system to switch to battery mode for battery
testing. Ensure bypass is available and battery capacity is greater than 25% before testing.
Battery support – Touching icon
Allows the system to switch to battery mode to check
the battery. Ensure bypass is available and battery capacity is greater than 25% before testing.
Boost charging – Touching icon
enables accelerated loading in boost mode.
Float charging – Touching icon
allows Float to load in normal mode.
Stop test – Touching icon
interrupts the battery test.
5.2.7
Scope
Touching icon
(In the lower right part of the panel), the system will switch to the
oscilloscope window display mode shown below.