HIDEAWAY
ACTIVE SENSOR-FLUSH URINAL
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
HIDEAWAY
ACTIVE SENSOR-FLUSH URINAL
12.0
Maintenance of the Solenoid Cartridge:
When performing maintenance on the flush valve or its components shut off the power and water supply and unplug
the solenoid sealed connector cable.
1) Unscrew the solenoid cartridge (if required use a 17mm socket).
2) Rinse and clean the strainer fitted to the solenoid cartridge.
3) Before re-installing the solenoid cartridge lubricate the two O-Rings
with a suitable tap O-Ring lubricant, Hydroseal tap lubricant or equivalent.
Note: Do not over-tighten. The max torque is 1Nm (hand-tight).
13.0
Spare parts
9503303 HIDEAWAY URINAL CONTROL UNIT 240V
9503304 HIDEAWAY URINAL SENSOR TRAP (NO SEALS)
9503305 HIDEAWAY URINAL 240V TRANSFORMER
9503306 HIDEAWAY URINAL SENSOR EXT CABLE (2.65M)
9503307 HIDEAWAY URINAL INLET & OUTLET SEAL
9503308 HIDEAWAY URINAL SHUTOFF VALVE
9503309 HIDEAWAY URINAL SOLENOID CARTRIDGE
9503310 HIDEAWAY URINAL SOLENOID BODY
9503311 HIDEAWAY URINAL AIR-BREAK
9503984 HIDEAWAY URINAL CONTROL BATTERY POW ERED (LESS BATTERY)
9503985 HIDEAWAY URINAL BATTERY 6V CR-P2
17mm socket
Sealed connector
cable
O-Rings
Strainer
page 15 of 16