background image

www.

reefe

.com.au

Ascento Group Australia

© 

AI.062020

P: 1800 807 604

              START UP  (SINGLE DEVICE)

Be sure that the pump is correctly primed

Connect the device to the electric supply with the magnetothermic switch, FAILURE led light will be ON. Wait for 10 seconds while the device is doing 

the autotest. Once it finishes, led light FAILURE is OFF and led light LINE is ON. The LCD screen will show message “SPEEDBOX ” and inmediately the 

language display of the configuration mode.

The device is ready for being configured.

               START UP (2 DEVICES ASSEMBLY)

If we wish to mount 2 devices for working in groups, previous point should be exactly followed - the order of connection is irrelevant. During the 

configuration process we will be able to choose which device is the 

MASTER

.

           CONFIGURATION

Using 



we can change the values and press 

ENTER

 for validation. Whenever we want to quit the configuration sequence press 

MENU

. After every 

ENTER

 it will appears automatically the different screens that constitute the configuration sequence.



 

MENU

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

P s e t

4 , 0

P b a r

3 , 9

P s e t

4 , 0

P b a r

3 , 9

L A N G U A G E

E N G L I S H

M A X . I N T

1 0

A

R O T A T I O N

0

M I N . F R E Q

1 5

H z

T Y P E

S I N G L E ?

P . S E N S O R

0 - 1 0

b a r

L E V E L ?

N O

OFF

START/

ON

P R E S S U R E

0 3 , 0

b a r

D I F

O N

0 , 5

By mean of keys          we can choose lanuages “LANGUAGE ENGLISH”, 

“LANGUE FRANCAISE, ”LINQUA ITALIANA” AND IDIOMA ESPANOL”

To start the configuration sequence press 

MENU 

ENTER 

during 3”

By mean of keys          input the nominal current intensity value in A of the pump enabling the thermal 

protection. This value is located over the characteristics plate of the motor. Press 

ENTER 

for validation.

WARNING: This value is linked with the flow detection system, it is very important to enter the exact 

current consumption indicated on the name plate. 

 



 

ROTATION SENSE. 

Using the 

START/STOP 

pushbutton verify the rotation sense. By mean of keys        (0/1) 

we can change it. Press 

ENTER 

for validation. 



 

MINIMUM FREQUENCY. 

Using 

 we can increase the lower frequency value, within 15-48 Hz for 3-phase 

pumps and 30-48 Hz for single-phase pumps.

*The minimum frequency value will be used as frequency stop in installations where the automatic detection of the device 

do not act due to leaks in the system. See hydraulic installation.  

EXTERNAL LEVEL SENSOR. 

If the installation does not have level probe 

press 

ENTER 

to validate NO.  

If the installation has a level probe, use keys  



 to change NO by Y. 

 

This will be the system operating pressure. Use keys 



 for modify the initial value (2 bar)

WARNING! The input pressure must be at least 1 bar lower than the maximum pressure of the pumps. 

NOTE: 

In case of group assembly, all system operates at the pressure set in the MASTER device, so that the 

configuration of set pressure in the slave device is superfluous. 

The default value is 0.5 bar. This value of pressure is substracted to the system setpoint, resulting the final 

pressure to which the system will set in motion the pump when the hydraulic network has a demand. Use 

keys pq to modify the initial value. It is recommended to maintain this value between 0.3 and 0.6 bar. 

Example:

- Input pressure: 2 bar 

- Differential start: 0.3 bar 

- Final start pressure: 2-0.6 = 1.4 bar. 

The device is configured by default as 

SINGLE. 

In case of individual assembly just confirm 

SINGLE 

by 

pushing 

ENTER. 

In case of group assembly (M-S), we will choose respectively 

SLAVE and MASTER 

in each 

unit pushing 

.

The range of lecture of the pressure transmitter installed must be adjusted. 

If the range is within 0-10 bar confirm by mean of 

ENTER.

If the range is within 0-16 or 0-25 bar change it by mean of 



 and then confirm with

 ENTER

After pressing 

ENTER 

pushbutton, the system is ready to operate. Press 

AUTOMATIC 

in order to quit manual 

mode. 

In case of group assembly press 

AUTOMATIC 

only in the device set as MASTER. 

In case of group assembly, after pressing 

AUTOMATIC

 in the 

MASTER

 device, the 

AUTOMATIC LED LIGHT

 of the 

SLAVE

 device will start to flash 

intermittently, indicating that communication between both devices is ready. If this does not happen verify the connection (Fig 5).

  

  

Summary of Contents for 21297

Page 1: ...om au EXPLODED VIEW INSTRUCTION MANUAL P U M P S A U S T R A L I A BETTER FASTER EASIER BETTER FASTER EASIER MODEL VSC1 10W VSC1 12W VSC3 9W VSC3 14W CODE 21297 21910 21934 21941 VARIABLE SPEED DRIVE...

Page 2: ...mm2 1 1 5 OUTPUT FILTER T T Maste Cavo d C ble Cable Maste Maste Kabel Pressu Trasdu Capte Transd Druks Druks Przetw Minim Livello Niveau Senso Extern Minim Minim Power Alimen Alimen Alimen Netza Voe...

Page 3: ...re doing any maintenance inside the device it must be unplugged from the electric supply and wait a minimum of 2 minutes after the disconnection to avoid electrical discharges WARNING SYMBOLS CONTAINE...

Page 4: ...its housing Screw the cover and the PG If the devices are provided with the communication cable it governs the following color code 1 black 2 brown 3 grey and 4 yellow blue They will be connected by...

Page 5: ...robe MAX MIN LEV N O CONTACT General Fuse Power Supply U V 1 240 V M Single Phase Motor Connection Three Phase Motor Connection U V W 3 240 V M Fig 3 CONNECTIONS VSC1 12W 240 VSC1 10W 15 V DC 24 V DC...

Page 6: ...er supply System is activated in AUTOMATIC mode keeping the configuration parameters see CONFIGURATION chapter External pressure transducer 4 20 mA under demand Possibility of communication with anoth...

Page 7: ...nd 4 In case of M S communication it will be connected a pressure transmitter in each unit Min level control optional There is an input for stopping the pump as soon as is disconnected the external sw...

Page 8: ...Press ENTER for validation MINIMUM FREQUENCY Using we can increase the lower frequency value within 15 48 Hz for 3 phase pumps and 30 48 Hz for single phase pumps The minimum frequency value will be...

Page 9: ...ng to the SET UP menu see the chapter configuration and configuring the adequate intensity values A3 DISCONNECTED P Final failure DESCRIPTION the device has an electronic safety system in case of no l...

Page 10: ...arms in both devices the system performs 4 restore attempts if it fails the system is disabled To restore manually a device disabled by an alarm push AUTOMATIC ON OFF in MASTER device and then ENTER i...

Reviews: