7.1

 

Requirements for initial commissioning  

The device will be ready for initial commissioning when the tasks described in 
the "Installation" chapter have been completed. Note the following information 
on initial commissioning: 
• 

The device is installed. 

• 

The water connections to the system circuit are established. 

• 

The device shut-off valves are closed. 
–  

Shut-off valve from the "DC" make-up line to the system circuit. 

–  

Shut-off valve of the "WC" make-up line to the fresh water main. 

• 

"PIS" pressure monitoring is ready. 

• 

The electrical connection has been created according to applicable 
national and local regulations. 

 

Establish a 230 V power supply by plugging the power plug into a corresponding 
outlet. The controller is in Stop mode. 
 

7.2

 

Determining the P

0

 minimum operating pressure for the 

controller 

The "P

0

" minimum working pressure for the device is used in system circuits with 

a diaphragm expansion vessel. 
Calculate the "P

0

" minimum working pressure for the device: 

 

 

 
• 

The device is installed at the same level as the diaphragm expansion 
vessel: 
–  

hst = 0, P0 = p0* 

• 

The device is installed at a lower level than the diaphragm expansion 
vessel: 
–  

P

0

 = p0 + h

st

/10* 

• 

The device is installed at a higher level than the diaphragm expansion 
vessel: 
–  

P

0

 = p0 - h

st

/10* 

 

 

*p0 in bar, h

st 

in metres 

 

 

Note! 
Calculate the filling pressure for system circuit make-up using fresh 
water as follows: 

Filling pressure ≥ P

0

 + 0.3 bar 

 

 

Note! 
When planning, note that the working range of the device must come 
within the pressurisation working range, which extends from the initial 
pressure "PA" to the final pressure "PE". 

 

7.3

 

Filling the device with water 

 CAUTION 

 

Risk of injury due to pump start-up 
Hand injuries may occur when the pump starts up if you turn the pump 
motor at the impeller using a screwdriver. 
• 

Switch the pump to a zero-volts state before turning the pump at the 
fan wheel with a screwdriver. 

 

ATTENTION 

 

Device damage due to pump start-up 
Pump damage may occur when the pump starts up if you turn the pump 
motor at the impeller using a screwdriver. 
• 

Switch the pump to a zero-volts state before turning the pump at the 
fan wheel with a screwdriver. 

 

 

Fill water into the device: 
1. 

Slowly open the shut-off valve in the "WC" make-up line from the mains 
separator tank. 
–  

The mains separator tank is filled with water from the fresh water 
main. 

2. 

Check the proper closing of the float valve in the mains separator tank. 
–  

Water must not flow from the device overflow. 

3. 

Slowly open the shut-off valve in the "DC" make-up line to the system. 
–  

The pressure line from the mains separator tank to the pump is filled 
with water from the mains separator tank. 

 

 

 

Vent the pump (1): 
4. 

Remove the vent screw from the pump and vent the pump until bubble-
free water escapes. 
–  

If necessary, manually turn the pump using a screwdriver at the fan 
wheel until bubble-free water escapes. 

5. 

Tighten the vent screw and ensure that is does not leak. 

 

The device is filled with water. 
 

7.4

 

Parametrising the controller in the Customer menu 

Use the Customer menu to display or correct system-specific values. In the 
course of commissioning, the factory settings must be adjusted for the system-
specific conditions. 
–  

For adjusting the default settings, see chapter 9.2 "Configuring settings in 
the controller" on
 page 11 . 

–  

For information about controller operation, see chapter 9.1 "Operator 
panel" on
 page 11 . 

 

7.5

 

Function test 

Perform a device function test. Check the following functions: 
• 

Make-up with fresh water. 

• 

Tightness of the float valve in the mains separator tank. 

 

Prior to the function test, provide the following prerequisites: 
• 

Set the device controller to manual mode, see chapter 8.1.2 "Manual 
mode" on
 page 10 . 

• 

Clean the dirt trap, see chapter 10.3 "Cleaning the dirt trap" on page 14 . 

Summary of Contents for Fillcontrol Auto Compact

Page 1: ...Fillcontrol Auto Compact 20 10 2020 Rev D GB Operating manual Original operating manual ...

Page 2: ...on 6 6 4 Switching and make up variants 7 6 5 Electrical connection 7 6 5 1 Terminal diagram 8 6 5 2 RS 485 interface 8 6 6 Installation and commissioning certificate 8 7 Commissioning 8 7 1 Requirements for initial commissioning 9 7 2 Determining the P0 minimum operating pressure for the controller 9 7 3 Filling the device with water 9 7 4 Parametrising the controller in the Customer menu 9 7 5 F...

Page 3: ...safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe the safety information can result in minor reversible injuries ATTENTION Damage to property The sign in combination with the signal word Attention indicates a situation where damage to the product itself or objects ...

Page 4: ...3 Maximum working pressure in bar 1 2 3 4 4 Function 1 FQIRA contact water meter optional accessory 2 Fillsoft optional accessory 3 Fillcontrol Auto Compact PIS Pressure sensor WC Fresh water make up line to the device LS Signal line for insufficient water switch DC Make up line to the system circuit LIS External signal line from a pressurisation unit The device controller uses the pump to regulat...

Page 5: ...pressure in bar 6 Installation DANGER Risk of serious injury or death due to electric shock If live parts are touched there is risk of life threatening injuries Ensure that the system is voltage free before installing the device Ensure that the system is secured and cannot be reactivated by other persons Ensure that installation work for the electric connection of the device is carried out by an e...

Page 6: ...ation 1 Position the device 2 Create the water side connections of the device to the system Use connections with the same dimensions at the device for all lines 3 If required create the interfaces according to the terminal plan 6 3 1 Fitting the add on components WC Connection of the make up line to the mains separator tank OC Connection of the mains separator tank overflow DC Connection of the ma...

Page 7: ...into the system circuit LIS Level sensor To monitor the filling level in the pressurisation unit WC Make up line to the device ST Dirt trap at the shut off valve of the mains separator tank BT Mains separator tank PU Pump PIS Pressure sensor LS Insufficient water switch DN Nominal diameter of the make up line Water make up to system circuits with a pressurisation unit Pressurisation units are equi...

Page 8: ...ontroller for example Set the controller to Levelcontrol User optional 17 Make up 230 V 18 Make up 230 V 22 PE shield Pressure analogue input For output to the display For make up actuation For the Magcontrol make up variant Factory 23 Pressure signal 24 Pressure 18 V 29 A RS 485 interface User optional 30 B 31 GND 32 24 V supply E1 Supply for E1 and E2 Pre wired bridged 33 E1 Contact water meter ...

Page 9: ...or at the impeller using a screwdriver Switch the pump to a zero volts state before turning the pump at the fan wheel with a screwdriver ATTENTION Device damage due to pump start up Pump damage may occur when the pump starts up if you turn the pump motor at the impeller using a screwdriver Switch the pump to a zero volts state before turning the pump at the fan wheel with a screwdriver Fill water ...

Page 10: ...e up functions 8 1 2 Manual mode Use For testing and maintenance tasks Start Press Manual on the controller The auto LED on the controller operating panel and PU in the display flash as visual indicators of manual operation Functions After starting the manual mode you can manually activate and deactivate the pump Proceed as follows Press OK on the controller s operating panel to activate the pump ...

Page 11: ...en the make up variants Levelcontrol and Magcontrol Magcontrol In system circuits with a diaphragm expansion vessel Levelcontrol in system circuits with a pressurisation unit Min op pressure 01 8 bar The system displays the Minimum working pressure message when you have set the Magcontrol make up variant Enter the value for the minimum operating pressure Note Calculation of minimum operating press...

Page 12: ...ormation about the software version 9 2 1 Customer menu The device controller is shipped with the following default settings Use the Customer menu to adjust these values to local conditions In special cases it is possible to further adjust the values in the Service menu Parameter Setting Comment Language DE Display language Parameter Setting Comment Fillcontrol XX Magcontrol For systems with diaph...

Page 13: ...th Magcontrol Set value for the maximum pressure has been exceeded Safety valve defective Pipe to system has insufficient diameter Check the actuating pressure of the safety valve Replace the safety valve Install new pipe to the system with sufficient diameter Quit 11 Make up volume Only if With water meter is activated in the Customer menu Set value of the water meter has been exceeded Leakage in...

Page 14: ...2 1 Customer menu on page 12 Minimum operating pressure P0 Safety valve pressure PSV x Annually 10 2 Exterior leak test Check the following device components for leaks PU pumps and screw fittings Seal any leaks at the connections or replace the connections if required Seal leaking screw connections or replace if required 10 3 Cleaning the dirt trap Clean the ST dirt trap according to the following...

Page 15: ... dismantling block off all water side connections to the device 2 Disconnect the system from the power supply and secure it against unintended reactivation 3 Disconnect the power cable of the device from the power supply 4 Disconnect and remove all cables from the terminals of the device controller 5 Undo all hose and pipe connections between the device and the system and remove them completely 6 ...

Page 16: ... D EN Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match the local conditions Typ Type P0 PSV Fabr Nr Serial No ...

Page 17: ...SI1416enD 11 20 Reflex Winkelmann GmbH Gersteinstraße 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com ...

Reviews: