Controller
— 03.09.2020 - Rev. A
English — 19
4.
Set the system-specific values for the individual areas.
–
Use the "Left" and "Right" buttons to select the display value.
–
Use the "Up" and "Down" buttons to change the display value.
–
Confirm your entries with "OK".
Press "i" to display a help text for the selected area.
Press "X" to cancel your input without saving the new settings. The
controller automatically opens again the list.
10.3.2
Default settings
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In specific cases, it is
possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Comment
Language
DE
Display language.
Minimum operating
pressure "P
0
"
1.8 bar
see chapter 8.2 "Reflexomat
switching points" on page 15 .
Next maintenance
12 months
Time left to the next due
maintenance.
Volt-free contact
YES
see chapter 10.3.3 "Messages"
on page 19 .
Make-up
Make-up "ON"
8 %
Make-up "OFF"
12 %
Maximum make-up
volume
0 Litres
Only if make-up has been
selected in the customer menu
with "With water meter Yes".
Maximum make-up time 30 minutes
Maximum make-up
cycles
6 cycles within 2
hours
Softening (Only if "With
softening Yes")
Shut off make-up
No
In the case of soft water residual
capacity = 0
Hardness reduction
8°dH
= Target – Actual
Maximum make-up
volume
0 Litres
Soft water capacity
0 Litres
Cartridge replacement
18 months
Replace cartridge.
Service menu
Parameter
Setting
Comment
Pressurisation
Compressor "ON"
P
0
+ 0.3 bar
Differential pressured added
to the "P
0
" minimum
operating pressure.
Compressor "OFF"
P
0
+ 0.4 bar
Differential pressured added
to the "P
0
" minimum
operating pressure.
"Compressor run time
exceeded" message
240 minutes
The message is displayed
after the compressor runs for
240 minutes.
Overflow line "CLOSED"
P
0
+ 0.4 bar
Differential pressured added
to the "P
0
" minimum
operating pressure.
Overflow line "OPEN"
P
0
+ 0.5 bar
Differential pressured added
to the "P
0
" minimum
operating pressure.
Maximum pressure
P
0
+ 3 bar
Differential pressured added
to the "P
0
" minimum
operating pressure.
Filling levels
Insufficient water "ON"
5 %
Insufficient water "OFF"
12 %
Solenoid valve in
overflow line "CLOSED"
90 %
Water volume per contact 10 litres/contact
Optional, if a contact water
meter is installed (such as
Fillset Impulse).
10.3.3
Messages
t
The messages are impermissible deviations from the normal state. They can be
output either via the RS-485 interface or via two floating message contacts.
The controller displays the messages with a help text.
Message causes can be eliminated by the operator or a specialist workshop. If
this is not possible, contact the Reflex Customer Service.
Note!
When the cause for the message is eliminated, you must acknowledge
the fault with "OK" at the controller's operator panel.
Note!
Floating contacts, setting in the Customer menu, see chapter 10.3
"Configuring settings in the controller" on page 18 .
To reset a fault message, proceed as follows:
1.
Touch the display.
–
The current fault messages are displayed.
2.
Touch a fault message.
–
The system displays the possible causes of the fault.
3.
When the fault is eliminated, confirm the fault with "OK".
ER
Code
Alarm
Causes
Remedy
Alarm reset
01
Min. pressure
•
Set value exceeded.
•
Water loss in the system.
•
Compressor fault.
•
Controller in Manual mode.
•
Check set value in the Customer or Service
menu.
•
Check water level.
•
Check compressor.
•
Set the controller to Automatic mode.
"OK"
02.1
02.2
Compressor 1 insufficient
water
Compressor 2 insufficient
water
•
Set value not reached.
•
Make-up disabled.
•
Air in the system.
•
Dirt trap clogged.
•
Check set value in the Customer or Service
menu.
•
If necessary, manually add water.
•
Check functioning of the "PV1" solenoid valve.
•
Clean the dirt trap.
–