Reflexomat XS — 02.16.2022 - Rev. A 

 

English  — 23 

 

 

Note! 
The change in the filling level and the vessel pressure are indicated in 
manual mode in the SmartControl app. 

 

9

 

Controller 

9.1

 

Reflex Control Smart 

Access to the Reflexomat XS is possible using the Reflex Control Smart app via a 
Bluetooth-connected smartphone or tablet. The app is available from the app 
store (Android or iOS), or via the QR code given below. 

 

 

 

The Reflex Control Smart app provides the following functions amongst others: 
• 

Intuitive and self-explanatory menu and operating guidance 

• 

Easy and quick commissioning (commissioning-wizard) 

• 

Querying of the system pressure 

• 

Individual configuration 

• 

Maintenance and troubleshooting wizard  

• 

Software updates for system control 

 

 

Note! 
Software updates for system control may only be executed via the app. 
New available software updates are automatically displayed in the app. 

 

9.2

 

Operator panel 

 

 

Auto button/LED 
• 

The Auto button starts operation after commissioning or from 
stop mode 

• 

The Auto LED illuminates green in Automatic mode 

• 

The Auto LED is off in stop mode 

Pressure LED 
• 

The Pressure LED comes on in automatic mode 

• 

The Pressure LED flashes if there is a fault or during increasing 
and decreasing of the pressure 

Level LEDs 
• 

The level LEDs indicate the filling level in the vessel. 
–  

High water 3.1 

–  

Auto mode 3 

–  

Low water 3.3 (make-up requirement) 

Stop button/LED 
• 

The stop button is for entering new values in the controller and 
for manual mode (maintenance mode) 

• 

The Stop LED lights up in yellow 

Service button/LED 
• 

Warning and fault messages are acknowledged with the Service 
button 

• 

The Service LED lights up in the event of a warning message 

• 

The Service LED flashes in the event of a fault message 

 

9.3

 

Default settings  

The device controller is shipped with the following default settings. Other 
settings must be made during assisted commissioning using the Reflex Control 
Smart app. 

 

Default settings 

Parameter 

Setting 

Comment 

Next maintenance 

12 months 

Time left to the next due 
maintenance. 

Floating contact 

YES 

 9.4 "Messages", 

 23. 

Make-up 

 

 

Make-up "ON" 

8 % 

 

Make-up "OFF" 

12 % 

 

Maximum make-up 
quantity 

0 Litres 

Only when using a water meter. 

Maximum make-up time  

30 minutes 

 

Maximum make-up cycles  6 cycles 

within 2 hours  

 

Pressure maintenance 

 

 

Compressor "ON" 

P

0

 + 0.3 bar  

Differential pressured added to 
the "P

0

" minimum operating 

pressure. 

Compressor "OFF" 

P

0

 +  0.4 bar 

Differential pressured added to 
the "P

0

" minimum operating 

pressure. 

"Compressor run time 
exceeded" message 

180 minutes 

The message is displayed in the 
app after compressor running of 
180 minutes. 

Outward flow solenoid 
valve "CLOSE" 

P

0

 + 0.4 bar 

Differential pressured added to 
the "P

0

" minimum operating 

pressure. 

Outward flow solenoid 
valve "OPEN" 

P

0

 + 0.5 bar 

Differential pressured added to 
the "P

0

" minimum operating 

pressure. 

Maximum pressure 

PSv – 0.3 bar 

Differential pressure as the 
triggering pressure of the 
response pressure of safety 
valve "PSv". 

Filling levels 

 

 

Low water "ON" 

5 % 

 

Low water "OFF" 

12 % 

 

Solenoid valve in overflow 
pipe "CLOSED" 

90 % 

 

 

 

9.4

 

Messages 

Messages are displayed using the LEDs on the control panel with the meanings 
specified in the table. A precise description of the LEDs, 

 9.2 "Operator panel", 

 23. A detailed description of the error is available via the app. 

LED 

Function / 
display 

Meaning 

Auto 

 

Button 

Start 

LED lights up 

Automatic operating mode 

Stop 

 

Button 

Maintenance / Interruption 

LED lights up 

Error 

Service 

 

Button 

Acknowledge / Start Self-
Service 

LED lights up 
LED flashes 

Warning 
Error 

Cooke Industries - Phone: +64 9 579 2185   Email: sales@cookeindustries.co.nz   Web: www.cookeindustries.co.nz

Summary of Contents for Reflexomat XS

Page 1: ...od na obsluhu CZ origin ln n vod k obsluze PL T umaczenie instrukcji oryginalnej LV Ori in l lieto anas pam c ba LT Originali naudojimo instrukcija EE Originaalkasutusjuhendi t lge NL Originele bedien...

Page 2: ...s 20 6 4 1 Function 20 6 5 Power Supply 21 6 5 1 Terminal diagram 21 6 5 2 RS 485 interface 21 6 6 Installation and commissioning certificate 21 7 Commissioning 21 7 1 Requirements for initial commiss...

Page 3: ...ilure to observe the safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to ob...

Page 4: ...tem pressure Max system pressure min operating pressure set up on site Minimum operating pressure set on site 4 4 Function 1 Make up with water e g using Fillcontroll Auto Servitec S 2 Control unit 3...

Page 5: ...ing capacity Up to approx 400 kW 5 2 Vessel Vessel without controller volume 80 l 6 Installation DANGER Risk of serious injury or death due to electric shock If live parts are touched there is risk of...

Page 6: ...icient side and top clearance Install the vessel on a level surface Ensure a perpendicular and free standing position Ensure proper functioning of the LIS Filling level measurement sensor Do not attac...

Page 7: ...oller When the water level falls below the set value the external make up is activated 6 4 1 1 Make up without pump Reflexomat XS with Fillvalve 1 Reflexomat XS WC Make up line 2 Fillvalve LIS Weight...

Page 8: ...states Operating states of make up via solenoid valve Aggregate volume of the FQIRA contact water meter All messages 9 4 Messages 23 All entries in the error memory 6 5 2 1 Connecting the RS 485 inte...

Page 9: ...troller The following prerequisites must be met for automatic mode The device is filled with compressed air and water All required parameters are defined in the controller Press Auto for automatic mod...

Page 10: ...ashes in the event of a fault message 9 3 Default settings The device controller is shipped with the following default settings Other settings must be made during assisted commissioning using the Refl...

Page 11: ...l any leak in the air system Check functioning of PV air side solenoid valve Check functioning of compressor Service 06 Make up time 1 Auto LED lights up 5 Error LED lights up 3 Level LED flashes Set...

Page 12: ...s are the following correct settings Minimum operating pressure P0 9 1 Reflex Control Smart 23 Filling level measurement in the primary vessel Preparation 1 Switch to Automatic mode 2 Close the cap va...

Page 13: ...ure that the system is secured and cannot be reactivated by other persons Ensure that installation work for the electric connection of the device is carried out by an electrician and in compliance wit...

Page 14: ...e Nastaven zen odpov d m stn m podm nk m PL Potwierdzenie monta u i rozruchu Urz dzenie zosta o zamontowane i uruchomione zgodnie z instrukcj obs ugi Ustawienie sterownika jest zgodne z lokalnymi waru...

Page 15: ...tes Notas Notas Note Jegyzetek Bele ke Pozn mky Pozn mky Notatki Pastabos Piez mes M rkmed Notities Noter Notater Anteckningar Merkinn t Noti e Notlar Cooke Industries Phone 64 9 579 2185 Email sales...

Page 16: ...Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com Cooke Industries Phone 64 9 579 2185 Email sales cookeindustries co nz Web...

Reviews: