Controller
12 — English
Master/Slave Operation — 24.09.2015
8. Switch to the next list item, "Max. pressure deviation".
– This parameter is meaningless in the master and can be ignored.
– Define the parameter in the slaves.
– Setting range 0.1 – 5.0 bar.
– Use the arrow keys to enter the parameter value.
– Press "OK" to confirm.
Max. pressure deviation:
dPmaxSL = 1.0 bar
9. Switch to the next list item, "Activation delay".
– The activation delay sets the activation behaviour of the optional second pump,
compressor or overflow valve.
– This parameter is meaningless in the master and can be ignored.
– Define the parameter in the slaves.
– Setting range 0–240 seconds.
– Use the arrow keys to enter the parameter value.
Activation delay:
LK/MK = 5 s
– Press "OK" to confirm.
10. Switch to the next list item, "Max. level deviation".
– This parameter is meaningless in the master and can be ignored.
– Define the parameter in the slaves.
– Setting range 0 – 20 %.
– Use the arrow keys to enter the parameter value.
Max. level deviation:
dNiv = 5 %
– Press "OK" to confirm.
11. Switch to the next list item, "Block message 29 PFK".
– Use the arrow keys to select each function.
Message 29 PFK
NO:
Select this function for the master.
The "29 Communication fault" message is output to the floating contact.
Block?
NO
YES: Select this function for the slaves.
The "29 Communication fault" message is not output to the floating
contact.
– Press "OK" to confirm.
Note!
You have completed the settings in the controllers when all parameters for the master and the slaves are entered.
– Ensure that all devices are set to Master/Slave operation.