Controller
46 — English
Vacuum spray degassing — 06.07.2016 - Rev. B
ER Code
Alarm
Floating contact
Cause
Remedy
Alarm reset
19
Stop
˃
4 hours
-
Device is in stop mode for more
than 4 hours.
Set the controller to
Automatic mode.
-
20
Maximum makeup
quantity
-
Set value exceeded.
Reset the "Makeup
quantity" meter in the
Customer menu.
Quit
21
Maintenance
recommended
-
Set value exceeded.
Carry out maintenance.
Quit
24
Softening
-
•
Set value for soft water
capacity exceeded.
•
Time interval for
replacement of the
softening cartridge
exceeded.
Replace the softening
cartridges.
Quit
30
I/O module fault
-
•
I/O module defective.
•
Connection between option
card and controller faulty.
•
Option card defective.
•
Replace the I/O
module.
•
Check the connection
between option card
and controller.
•
Replace the option
card.
-
31
EEPROM defective
Yes
•
EEPROM defective.
•
Internal calculation error.
Inform Reflex Customer
Service.
Quit
32
Undervoltage
Yes
Supply voltage not achieved.
Check power supply.
-
33
Adjustment
parameter faulty
-
EPROM parameter memory
defective.
Inform Reflex Customer
Service.
Quit
34
Main board
communication
faulty
-
•
Connecting cable defective.
•
Main board defective.
Inform Reflex Customer
Service.
Quit
35
Digital input voltage
faulty
-
Short-circuit of input voltage.
Check the wiring at the
digital inputs (water
meter, for example).
-
36
Analogue input
voltage faulty
-
Short-circuit of input voltage.
Check the wiring at the
analogue inputs
(pressure/level).
-
37
No input voltage at
the 3-ways motor
ball valve
-
Short-circuit of input voltage.
Check the wiring at the 3-
ways motor ball valve.
-