Page 2/2

Display Overview & Easy Start

Speed Search 

(CON71)

Bit #
1     During general acceleration
2     Initialization after a fault
3     Restart after instantaneous power  

interruption.

4   Starting with power on

2c) 

The mode button  sequences 
through the above modes, 'PAR' 
and 'CNF' are used in this guide.

1. POWER UP

Multi-Key
Function

N:

None 

U: User Group

FWD, 

REV

2b) 

Press

8 times 

scrolling

to '61'

3. EXECUTE "EASY START" FUNCTION

Operating Status:

STP: Stop
FWD: Forward

See manual for full list

Speed 
Reference:

K

: Keypad

V: V1 Input

See manual

for full list

Navigating Parameters:

With
displayed, press right
arrow to sequence through 
parameter groups. (DRV, BAS, 

ADV, etc.

Use down arrow to 

acces any code within each 
group.

2. INITIATE "EASY START" FUNCTION

2a) 

      

press

4 times 

Press

The parameters below will  be sequenced as shown in the order below after user input for 
each. The parameters in 

red

listed below have additional details shown at the bottom of the 

page.  Please refer to the User Manual for more details.

Be ready to enter the value for the parameter code shown:

1)

Macro selection

7)

Fault Restart 

(PRT08)

2) 60/50Hz   

(BAS10)

8) Motor Voltage 

(BAS15

)

3) Motor Capacity in HP  

(DRV14)

9) Retry Number 

(PRT09)

4) Rated Motor Current 

(BAS13)

10) Power On Resume (COM96

)

5) Motor Poles 

(BAS11)

11) 

Speed Search 

(CON71)

6) Line Voltage 

(BAS19)

12) CMD Source (use default)
13) Freq. Ref Src. (use default)

Fault Restart (Auto Restart on Power Loss) 

(PRT08)

Use

Bit:

on

off  

                                                   

Bit 0:   fault trips excluding
Low Voltage - move to high 
position

Bit 1:   fault trip 
exclusively for Low 
Voltage - move bit to 
high position

When you see this screen, 
you have completed quick 
start and are ready to run in

auto mode

.  If the start 

command is landed on P1, 

cycle power, 

and basic set

up is  complete.  Please refer 
to the manual for PID set 

To  Operate the VFD in Hand Mode:

Multi-directional key is used to 
select the speed in Hz.

The motor will start accelerating 

Initial

display at 

power up 

Start 
Command:

K

Keypad

T: Terminal 

Block

See manual

for full list

The Easy Start option should appear on

initial

power up.  Select YES to enter the Easy Start 

menu and proceed to step 3.  

If it does not appear on the first startup, then follow steps 2a,

2b, 2c.

This function will set up motor data, permit selection of a macro, and configure automatic 
restart criteria. If you are using an analog speed reference, and are using P1 on the terminal 
block, this will permit operation in auto mode in only a few minutes.

14 times 

scrolling

to '40'

press

& select 

Press

cycle 

power, easy 

start function 

will begin

Macro Select

If you see an application in the macro list that fits 
your needs select it, if not then select Basic.
Be aware the PID controller is enabled for all 
selections except Constant Torque.

If you want to run Easy Start again, simply repeat step 2 & 3.

Bit #
4 3 2 1