Software options
2016-08-05
117/330
V04.52
4
Definition of reference values after the completion of a function
sequence (“After Function Sequence finished”)
After a function sequence has been completed, a reference value can
be defined as follows:
“ VOLTAGE OFF” (“Voltage off”)
The device output is electrically isolated.
Actual reference values are retained directly from the function
block (“Hold level”).
From the active set value interface.
Set values are defined via this interface.
Maximum number of function sequences in the TopCon power
supply:
Up to 256
time-dependent standard function sequences
.
In the case of
arbitrary time-dependent (user-defined) func-
tion sequences
the number is dependent on the number of
points.
A maximum of 1000 points is possible.
In the case of
arbitrary function sequences
(user-defined AAP)
the number is dependent on number of points.
A maximum of 64 points is possible; these points can be distrib-
uted unevenly.
The function sequences saved in the power supply can be called via the
following interfaces:
HMI (RCU).
RS-232 interface.
TopControl application.
Using custom programs via function libraries.